Inspections for the day of: Thursday, December 17, 2009.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02035 FIRE-Final Inspection12/16/200912/17/200912/17/2009 3:49:41 PMPFAIL
The project related fire alarm permit needs to be addressed prior to life safety inspection.
BLD09-02120 FIRE-Final Inspection12/16/200912/17/200912/17/2009 3:42:46 PMPFAIL
all itmes have been corrected except an engineering report is needed for the grease duct per Dixie. This may effect the hood suppresion system.
BLD09-01808 FIRE-Final Inspection12/17/200912/17/200912/17/2009 3:14:49 PMPCANC
Randy Phone #: ###-#### Per Randy one of the residence rooms is not complete so the inspection is to be rescheduled.
BLD09-01947 FIRE-Final Inspection12/17/200912/17/200912/17/2009 2:57:26 PMPFAIL
See the city approved plans for the locations of the deficiencies. They include adding emergency lighting in the main lobby area and removing the thumbturn locks and providing lever hardware at two locations.
BLD09-01958 FIRE-Final Inspection12/16/200912/17/200912/17/2009 12:59:11 PMAPASS
life safety passed.