Inspections for the day of: Friday, December 17, 2010.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02798 Final12/17/201012/17/201012/17/2010 3:04:52 PMPPASS
air conditioner is on roof need extension ladder to access.Downtown hound name of business. Phone #: ###-#### >> Inspection requested via web by Fabian Luna ok final
ELE10-02410 Electrical Rough-In12/17/201012/17/201012/17/2010 2:46:42 PMPPASS
Ken-Please call at least 30 mins prior to inspection Phone #: ###-#### looked at raceway under floor for future use, ok to cover
ELE10-02122 Final12/16/201012/17/201012/17/2010 2:45:27 PMPFAIL
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby called, left correction notice, 210.52(A)(1) shall install receptacles in 2' walls entering mbr, 210.8(A)(7) shall provide gfci receptacle within 6' of sink in laundry room, 110.3(B) listed equipment shall operate per listings- 4 way switching upper hall
ELE10-01164 Rough-In Permanent Service12/16/201012/17/201012/17/2010 1:39:43 PMPPASS
>> Inspection requested via web by Terry Scott ri ok, p/s o/h n ok
ELE10-02790 Permanent Service12/17/201012/17/201012/17/2010 12:55:00 PMPFAIL
Jared is the electrician. Phone #: ###-#### >> Inspection requested via web by joel smith called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 300.5 direct burial shall be 24" deep, 230.24(A) service conductors shall be 8' over roof surface, BCC shall post job id sticker, shall post address, NOTE shall locate ground rods
ELE10-02791 Permanent Service12/17/201012/17/201012/17/2010 10:54:47 AMPPASS
Contact: Lyle Dean Phone #: ###-#### >> Inspection requested via web by Deb Gooden p/s u/g n ok
ELE10-02194 Final12/16/201012/17/201012/17/2010 10:34:37 AMPPASS
Final inspection. Back door should be open. Call if there are any problems or questions. Thanks Phone #: ###-#### >> Inspection requested via web by Eric Schroeder ok to final
ELE09-02216 Conference12/16/201012/17/201012/17/2010 9:58:35 AMADONE
James please make after 9:30 if possible Phone #: ###-#### called and asked owner to re-schedule for next week
ELE10-02556 Final12/16/201012/17/201012/17/2010 9:57:34 AMACANC
Phone #: ###-#### >> Inspection requested via web by JENNY EMEL inspection done by 445 on 12-16-10
ELE10-02008 DOC - Permit Finaled12/17/201012/17/201012/17/2010 9:16:31 AMAPASS
not in city, should be State permit
ELE10-02039 Final12/17/201012/17/201012/17/2010 8:50:02 AMAPASS
ok
ESC09-00378 Site Final12/17/201012/17/201012/17/2010 8:48:38 AMAPASS
ok final
ELE10-02399 Electrical Rough-In12/16/201012/17/201012/17/2010 8:26:45 AMAPASS
stan - ceiling cover Phone #: ###-#### called, told to be sure to add showroom receptacle in new addition area, ok cover ceiling only
ELE10-02025 ELE-Aging Inspection12/17/201012/17/201012/17/2010 6:21:38 AM DONE
see final
ELE10-02025 Final12/17/201012/17/201012/17/2010 6:21:26 AMAPASS
ok
ELE10-02069 ELE-Aging Inspection12/17/201012/17/201012/17/2010 6:20:24 AM DONE
suc
ELE10-02055 ELE-Aging Inspection12/17/201012/17/201012/17/2010 6:19:09 AM DONE
no activity, suc