Inspections for the day of: Monday, December 17, 2012.
Number of inspections: 17
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS12-00344 ELE-Conference12/13/201212/13/2012 P 
ELE11-00736 ELE-Aging Inspection12/17/201212/17/201212/21/2012 2:23:11 PM DONE
Stop by job site, discussed with home owner. electrical inspections were incomplete Bonding issues exsist
ELE12-01131 Final12/17/201212/17/201212/17/2012 4:49:05 PMPNR
brian Phone #: ###-#### need information on areas to inspect
ELE12-03040 Final12/16/201212/17/201212/17/2012 3:49:53 PMPNR
Swimming pool electrical. Access thru gate on right side of residence. Phone #: ###-#### >> Inspection requested via web by Lars Johnson Not ready for final
ELE12-03040 Electrical Rough-In12/17/201212/17/201212/17/2012 3:48:33 PMPPASS
rough-in ok cover pool underground and bonding
ELE12-03046 Final12/17/201212/17/201212/17/2012 2:25:24 PMPPASS
Hot tub around back Phone #: ###-#### >> Inspection requested via web by shane vigil final ok
ELE12-02198 Final12/17/201212/17/201212/17/2012 1:58:01 PMPPART
partial final for kitchen area only
ELE12-02198 Electrical Rough-In12/17/201212/17/201212/17/2012 1:57:31 PMPCANC
kitchen Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin
ELE12-02843 Final12/17/201212/17/201212/17/2012 1:41:06 PMPNR
WARREN PLEASE CALL 30 MIN BEFORE GOING OUT Phone #: ###-#### Not ready
ELE12-02843 Permanent Service12/17/201212/17/201212/17/2012 1:40:06 PMPFAIL
power reconnected by electrical contractor, NEC 300.4 nail plates, Shall identify grounding conductors. Shall terminate water pipe bonding conductor at first service disconnect.
ELE12-02461 Final12/17/201212/17/201212/17/2012 12:44:04 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Celinda Winters Main gate controler metal j-box not bonded, seal tight flex not strapped
ELE12-03043 Permanent Service12/17/201212/17/201212/17/2012 12:18:57 PMPPASS
100 amp service on a pole feeding a new portable office trailer. Call Jimmy for questions. ###-#### Phone #: ###-#### >> Inspection requested via web by John Edwards p/a o/h n ok
ELE12-03012 Conference12/17/201212/17/201212/17/2012 10:26:43 AMPDONE
Discuss with electrical contractor requirements for conduit burial depts
GCE12-00184 GCE-Final12/14/201212/17/201212/17/2012 9:35:33 AMAPASS
(Mandatory Inspection) correction completed final ok
ELE12-02743 Final12/14/201212/17/201212/17/2012 9:26:52 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl final ok
ELE12-02198 Electrical Rough-In12/17/201212/17/201212/17/2012 8:53:18 AMAFAIL
kitchen Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin not all receptacle have GFCI protection
ELE12-02701 Final12/14/201212/17/201212/17/2012 8:21:09 AMAPASS
Key on top of the electrical meter at back of house. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan correction complete final ok