Inspections for the day of: Tuesday, December 17, 2013.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00721 INSP-Final Inspection12/17/201312/17/201312/18/2013 4:53:20 PMPPASS
FIR12-00723 INSP-Final Inspection12/17/201312/17/201312/18/2013 4:52:40 PMPPASS
FIR13-00011 INSP-Final Inspection12/17/201312/17/201312/18/2013 4:51:41 PMPPART
Final pending trip times at dry systems floor levels 3, 4, and 5 per plan review notes item #2 and alternate agreement letter.
FIR13-00133 INSP-Final Inspection12/17/201312/17/201312/18/2013 4:49:42 PMPPASS
FIR12-00634 INSP-Final Inspection12/17/201312/17/201312/18/2013 4:49:08 PMPPASS
FIR12-00681 INSP-Final Inspection12/17/201312/17/201312/18/2013 4:48:34 PMPPASS
BLD13-00342 FIRE-Final Inspection12/17/201312/17/201312/17/2013 3:17:17 PMPPASS
Scope of work passed inspection. Missing escutcheon at the entryway closet to be replaced per contractor. Suite identification pending corridor finishes. PFE at the corridor are due annual certification.
FIR13-00678 INSP-Sprinkler Rough-in12/16/201312/17/201312/17/2013 2:54:19 PMPPART
Rough-in work completed. Need to adjust spacing and provide matched response heads in one area at the electrical and riser rooms.
FIR12-00500 INSP-Final Inspection12/17/201312/17/201312/17/2013 11:32:07 AMAPASS
Fire sprinkler permit finaled.
FIR12-00500 FIR-Aging Inspection12/17/201312/17/201312/17/2013 11:31:23 AM DONE
Ready for final
FIR12-00443 FIR-Aging Inspection12/17/201312/17/201312/17/2013 11:25:55 AM DONE
In progress
FIR12-00586 INSP-Supply line flush12/17/201312/17/201312/17/2013 11:23:54 AMAPART
UG fire supply line flush completed acceptable