ELE00-03086
| Final | 12/16/2013 | 12/17/2013 | 12/17/2013 2:32:20 PM | P | FAIL |
|
|
John Phone #: ###-#### NEC 406.11 All 15 and 20 ampere 120 volt receptacles shall be listed tamper-resistant . Clothes closets NEC 410.16(A)(1) recessed luminaire shall have completely enclosed lamp. Correct reverse polarity in receptacles
|
ELE13-03476
| Rough-In Permanent Service | 12/16/2013 | 12/17/2013 | 12/17/2013 2:01:05 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson rough-in p/s u/g n ok
|
ELE13-02453
| Final | 12/16/2013 | 12/17/2013 | 12/17/2013 1:35:27 PM | P | FAIL |
|
|
John Phone #: ###-#### NEC 210.8 (2) All kitchen 15 and 20 ampere receptacles shall have GFCI protection NEC 210.52(B)(3) Kitchen countertop shall be supplied by no fewer than two small appliance branch circuits. NEC 406.11 All 15 and 20 ampere 120 volt receptacle in dwelling units shall be listed tamper resistant receptacles
|
ELE13-03487
| Rough-In Permanent Service | 12/17/2013 | 12/17/2013 | 12/17/2013 1:20:59 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman rough-in p/s u/g n ok
|
ELE13-03473
| Electrical Rough-In | 12/16/2013 | 12/17/2013 | 12/17/2013 12:55:30 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Berthelot rough-in ok cover
|
ELE13-03125
| Electrical Rough-In | 12/17/2013 | 12/17/2013 | 12/17/2013 12:01:01 PM | P | PASS |
|
|
Contact: Tom Hartung - scan room wall inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover
|
ELE12-00802
| ELE-Aging Inspection | 12/17/2013 | 12/17/2013 | 12/17/2013 10:06:05 AM | | DONE |
|
|
still under construction
|
ELE12-01363
| ELE-Aging Inspection | 12/17/2013 | 12/17/2013 | 12/17/2013 10:04:19 AM | | DONE |
|
|
see final
|
ELE12-01363
| Final | 12/17/2013 | 12/17/2013 | 12/17/2013 10:02:43 AM | A | PASS |
|
|
UL listed sign final ok
|
ELE12-00316
| ELE-Aging Inspection | 12/17/2013 | 12/17/2013 | 12/17/2013 9:57:56 AM | | DONE |
|
|
see final
|
ELE12-00316
| Final | 12/17/2013 | 12/17/2013 | 12/17/2013 9:56:56 AM | A | PASS |
|
|
job complete, final ok
|
ELE13-01953
| Final | 12/16/2013 | 12/17/2013 | 12/17/2013 9:36:29 AM | A | PASS |
|
|
corrections made ready for final Phone #: ###-#### >> Inspection requested via web by Don Lustig job complete, final ok
|
ELE13-03493
| Conference | 12/16/2013 | 12/17/2013 | 12/17/2013 9:23:43 AM | A | DONE |
|
|
Call troy Phone #: ###-#### >> Inspection requested via web by Don Conley Discussed electrical requirements for code violation area, family room,bathroom conversion
|
ELE13-03464
| Rough-In Permanent Service | 12/17/2013 | 12/17/2013 | 12/17/2013 8:50:01 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-in p/s u/g n ok
|
ELE12-01913
| Final | 12/10/2013 | 12/17/2013 | 12/17/2013 8:17:39 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Louis Keller job complete, final ok
|
ELE11-02728
| ELE-Aging Inspection | 12/17/2013 | 12/17/2013 | 12/17/2013 7:03:39 AM | | DONE |
|
|
still under review
|