ELE15-03796
| Final | 12/17/2015 | 12/17/2015 | 12/17/2015 3:30:36 PM | P | FAIL |
|
|
El Habenero Taco Truck Phone #: ###-#### Inspection requested via web by Celinda Winters 210.8(B)(2)-All 15 and 20 amp receptacles in other than dwelling kitchens shall have GFCI protection
|
ELE15-03037
| Final | 12/17/2015 | 12/17/2015 | 12/17/2015 2:10:07 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt final ok
|
ELE14-03316
| Electrical Rough-In | 12/16/2015 | 12/17/2015 | 12/17/2015 1:34:09 PM | P | PASS |
|
|
Garage Expansion, Room 121;122. Branch circuits Phone #: ###-#### Inspection requested via web by Tom Betty r/i walls ok
|
ELE15-03937
| Electrical Rough-In | 12/16/2015 | 12/17/2015 | 12/17/2015 11:36:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender r/i walls ok EXCEPT electrical room and panel
|
ELE15-04030
| Final | 12/17/2015 | 12/17/2015 | 12/17/2015 10:48:20 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by David Green needed p/s
|
ELE15-04030
| Permanent Service | 12/17/2015 | 12/17/2015 | 12/17/2015 10:47:18 AM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Green As per manufacturers instructions on door, 70 amp maximum breaker except at lowest position. 250.53(a)(2)- additional ground rod required unless 25 ohms or less to earth
|
ELE15-02953
| Final | 12/16/2015 | 12/17/2015 | 12/17/2015 10:18:23 AM | A | PASS |
|
|
Homeowner will be home. Final of new addition Phone #: ###-#### Inspection requested via web by Steve Craig final ok
|
ELE15-03773
| Final | 12/16/2015 | 12/17/2015 | 12/17/2015 10:07:04 AM | A | PASS |
|
|
please call Chris ###-#### to be let in the house ...at least 45 minutes in advance. Thank You Phone #: ###-#### Inspection requested via web by Chris Husted final ok
|
GCE15-00175
| GCE-Rough-In Permanent Service | 12/16/2015 | 12/17/2015 | 12/17/2015 9:24:48 AM | A | FAIL |
|
|
Brandon ###-#### Dnst. bath vanity nm cable not installed in box. Garage receptacle nm cable not installed in box. 300.4(a)(1)-11/4" clearance required from bored hole to edge of stud. Nm cable within 6' of crawl needs protection
|