Inspections for the day of: Thursday, December 17, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03796 Final12/17/201512/17/201512/17/2015 3:30:36 PMPFAIL
El Habenero Taco Truck Phone #: ###-#### Inspection requested via web by Celinda Winters 210.8(B)(2)-All 15 and 20 amp receptacles in other than dwelling kitchens shall have GFCI protection
ELE15-03037 Final12/17/201512/17/201512/17/2015 2:10:07 PMPPASS
Phone #: ###-#### Inspection requested via web by John VanZandt final ok
ELE14-03316 Electrical Rough-In12/16/201512/17/201512/17/2015 1:34:09 PMPPASS
Garage Expansion, Room 121;122. Branch circuits Phone #: ###-#### Inspection requested via web by Tom Betty r/i walls ok
ELE15-03937 Electrical Rough-In12/16/201512/17/201512/17/2015 11:36:22 AMAPASS
Phone #: ###-#### Inspection requested via web by kendall bender r/i walls ok EXCEPT electrical room and panel
ELE15-04030 Final12/17/201512/17/201512/17/2015 10:48:20 AMACANC
Phone #: ###-#### Inspection requested via web by David Green needed p/s
ELE15-04030 Permanent Service12/17/201512/17/201512/17/2015 10:47:18 AMPFAIL
Phone #: ###-#### Inspection requested via web by David Green As per manufacturers instructions on door, 70 amp maximum breaker except at lowest position. 250.53(a)(2)- additional ground rod required unless 25 ohms or less to earth
ELE15-02953 Final12/16/201512/17/201512/17/2015 10:18:23 AMAPASS
Homeowner will be home. Final of new addition Phone #: ###-#### Inspection requested via web by Steve Craig final ok
ELE15-03773 Final12/16/201512/17/201512/17/2015 10:07:04 AMAPASS
please call Chris ###-#### to be let in the house ...at least 45 minutes in advance. Thank You Phone #: ###-#### Inspection requested via web by Chris Husted final ok
GCE15-00175 GCE-Rough-In Permanent Service12/16/201512/17/201512/17/2015 9:24:48 AMAFAIL
Brandon ###-#### Dnst. bath vanity nm cable not installed in box. Garage receptacle nm cable not installed in box. 300.4(a)(1)-11/4" clearance required from bored hole to edge of stud. Nm cable within 6' of crawl needs protection