FIR19-00274
| INSP-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 2:58:41 PM | P | FAIL |
|
|
Chute room on level 3 is also a furnace closet, sprinkler head must be provided in mechanical closets. 4 sprinkler heads are less than 24 inches from heat registers, sprinklers must be 24 inches or greater away from heat registers per 2016 NFPA 13D. Repair holes around sprinkler heads where escutcheon does not cover entire penetration. Install escutcheons that are missing as discussed and replaced escutcheon in master bathroom.
Please call before heading to job site. We will be coming from the office and will need about 30 to 45 minutes to get to the job site. Phone #: ###-#### Inspection requested via web by Matt Barnard
|
BLD19-02586
| FIRE-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 12:16:40 PM | A | PASS |
|
|
Final life fire safety inspection for scope of work is complete.
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer
|
FIR19-00390
| INSP-Sprinkler Rough-in | 12/16/2019 | 12/17/2019 | 12/17/2019 12:16:12 PM | A | PART |
|
|
Due to this being a steep hiilside project, undergorund supply approved for partial cover, fittings to be left exposed and will be inspected following day.
UG Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD19-02053
| BLD-Conference | 12/16/2019 | 12/17/2019 | 12/17/2019 11:19:16 AM | A | DONE |
|
|
Fire conference complete.
Ron Phone #: ###-####
|
FIR19-00666
| INSP-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 10:13:39 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|
BLD19-04783
| FIRE-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 9:53:06 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire exitnguisher is placed and will be inspected as discussed. Final life fire safety inspection complete, signature provided on permit sign off card.
JANA Phone #: ###-####/
|
BLD19-01829
| FIRE-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 9:35:24 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modificaitons required, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work is complete, no signature card provided at time of inspection.
Adam Phone #: ###-####
|
BLD19-01829
| FIRE-Supply Line Hydro | 12/16/2019 | 12/17/2019 | 12/17/2019 9:33:50 AM | A | CANC |
|
|
Adam Phone #: ###-####
|
BLD19-03260
| FIRE-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 8:37:32 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modifications required, fire extinguishers are placed and will be tagged with current inspection tags. Final life fire safety inspection for area of work is complete.
Daryl Phone #: ###-####
|
FIR19-00846
| INSP-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 8:36:36 AM | A | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.
Contact Hunter Anderson - ###-#### Final Insp - Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00846
| INSP-Final Inspection | 12/16/2019 | 12/17/2019 | 12/16/2019 12:02:56 PM | P | CANC |
|
|
Contact Hunter Anderson ###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|