| FIRE-Final Inspection | 12/18/2006 | 12/18/2006 | 12/19/2006 3:10:18 PM | P | PASS |
|
|
Fire life safety inspection passed, two exit signs at the service bay south to be repaired ASAP as agreed.
|
BLD06-03150
| FIRE-Final Inspection | 12/15/2006 | 12/18/2006 | 12/19/2006 3:00:07 PM | A | NR |
|
|
Project is not yet complete for final fire inspection.
|
FIR06-00102
| FIR-Aging Inspection | 12/18/2006 | 12/18/2006 | 12/19/2006 12:55:37 PM | | DONE |
|
|
|
FIR06-00607
| INSP-Final Inspection | 12/18/2006 | 12/18/2006 | 12/19/2006 9:46:18 AM | P | PART |
|
|
The vent tube is missing at the duct detector in the mech mezzanine, need to provide verification of adequate air flow at two duct detectors due to installation locations.
|
FIR06-00496
| INSP-Final Inspection | 12/15/2006 | 12/18/2006 | 12/19/2006 9:43:15 AM | A | PART |
|
|
Need to provide pressure relief valve for the grid system, provide "911" sign at the bell.
|
FIR06-00809
| INSP-Final Inspection | 12/18/2006 | 12/18/2006 | 12/19/2006 9:41:47 AM | P | PASS |
|
|
Corrections verified, final fire sprinkler inspection passed.
|
FIR05-00772
| INSP-Sprinkler Rough-in/Hydro | 12/15/2006 | 12/18/2006 | 12/18/2006 2:31:54 PM | A | PART |
|
|
OH hydrostatic testing for the two dry systems and the single wet system passed. Also approved the rough-in installation for cover at the office area. Still need to perform 24 hr. air test on the dry systems per NFPA, noted missing flex couplings at the riser and provision for forward flow testing of the BFP.
|
FIR06-00879
| INSP-Final Inspection | 12/15/2006 | 12/18/2006 | 12/18/2006 2:01:42 PM | A | PASS |
|
|
Fire alarm installation passed final inspection, permit finaled.
|
BLD04-01349
| FIRE-Final Inspection | 12/18/2006 | 12/18/2006 | 12/18/2006 2:00:44 PM | A | PASS |
|
|
Life safety passed inspection, the provided fire extinguishers on site to be mounted on the walls at locations as agreed, one "sticking" exit door threshold at the first floor south to be repaired prior to structural final.
|
BLD06-03218
| FIRE-Alarm Testing | 12/17/2006 | 12/18/2006 | 12/18/2006 1:57:08 PM | A | FAIL |
|
|
Existing fire sprinkler heads at the bar area do not meet min. code requirements with regard to spacing, temp. ratings are mixed, escutcheons are missing, one head is painted, also missing max. occupant load sign per review notes, existing fire alarm notification devices have been painted black and some lenses are obscured. A fire permit will be required for modifications or alterations made to existing sprinkler or alarm systems.
|