Inspections for the day of: Monday, December 18, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-00275 FIRE-Final Inspection12/18/200612/18/200612/19/2006 3:10:18 PMPPASS
Fire life safety inspection passed, two exit signs at the service bay south to be repaired ASAP as agreed.
BLD06-03150 FIRE-Final Inspection12/15/200612/18/200612/19/2006 3:00:07 PMANR
Project is not yet complete for final fire inspection.
FIR06-00102 FIR-Aging Inspection12/18/200612/18/200612/19/2006 12:55:37 PM DONE
FIR06-00607 INSP-Final Inspection12/18/200612/18/200612/19/2006 9:46:18 AMPPART
The vent tube is missing at the duct detector in the mech mezzanine, need to provide verification of adequate air flow at two duct detectors due to installation locations.
FIR06-00496 INSP-Final Inspection12/15/200612/18/200612/19/2006 9:43:15 AMAPART
Need to provide pressure relief valve for the grid system, provide "911" sign at the bell.
FIR06-00809 INSP-Final Inspection12/18/200612/18/200612/19/2006 9:41:47 AMPPASS
Corrections verified, final fire sprinkler inspection passed.
FIR05-00772 INSP-Sprinkler Rough-in/Hydro12/15/200612/18/200612/18/2006 2:31:54 PMAPART
OH hydrostatic testing for the two dry systems and the single wet system passed. Also approved the rough-in installation for cover at the office area. Still need to perform 24 hr. air test on the dry systems per NFPA, noted missing flex couplings at the riser and provision for forward flow testing of the BFP.
FIR06-00879 INSP-Final Inspection12/15/200612/18/200612/18/2006 2:01:42 PMAPASS
Fire alarm installation passed final inspection, permit finaled.
BLD04-01349 FIRE-Final Inspection12/18/200612/18/200612/18/2006 2:00:44 PMAPASS
Life safety passed inspection, the provided fire extinguishers on site to be mounted on the walls at locations as agreed, one "sticking" exit door threshold at the first floor south to be repaired prior to structural final.
BLD06-03218 FIRE-Alarm Testing12/17/200612/18/200612/18/2006 1:57:08 PMAFAIL
Existing fire sprinkler heads at the bar area do not meet min. code requirements with regard to spacing, temp. ratings are mixed, escutcheons are missing, one head is painted, also missing max. occupant load sign per review notes, existing fire alarm notification devices have been painted black and some lenses are obscured. A fire permit will be required for modifications or alterations made to existing sprinkler or alarm systems.