Inspections for the day of: Tuesday, December 18, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03249 ELE-Aging Inspection12/18/200712/18/200712/20/2007 10:56:20 AM DONE
see final
ELE07-03871 Electrical Rough-In12/18/200712/18/200712/18/2007 4:11:34 PMPPASS
randy Phone #: ###-#### ok to backfill concrete encased electrode, ric ok garage and new building, will call for final later
ELE07-03827 Final12/18/200712/18/200712/18/2007 3:29:11 PMPPASS
chad Phone #: ###-#### - please call 1/2 hr prior to inspection ok to final
ELE07-03829 Final12/18/200712/18/200712/18/2007 2:30:07 PMPPASS
chad Phone #: ###-#### - please call 1/2 hr prior to inspection called contractor, ok to final
ELE07-03828 Final12/18/200712/18/200712/18/2007 1:55:31 PMPPASS
chad Phone #: ###-#### - please call 1/2 hr prior to inspection occupied, could only spot check receptacles, ok to final
ELE07-04159 Conference12/18/200712/18/200712/18/2007 12:57:01 PMPDONE
Charlie. Next door to Riverside Embroidery at Travlers Motel Phone #: ###-#### Internet Inspection Request from: Charles Davis talked about service for burnt service to motel, told to get grounding up to date, irreversible connection for ground, add 2 ground rods, provide clearance over roof and incoming
ELE07-04136 Rough-In Permanent Service12/18/200712/18/200712/18/2007 10:26:57 AMACANC
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman wrong type request, see ri
ELE07-04136 Electrical Rough-In12/18/200712/18/200712/18/2007 9:51:57 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ric ok, added sub-panel ok
ELE07-04147 Rough-In Permanent Service12/17/200712/18/200712/18/2007 9:45:12 AMAFAIL
Electrician is Nick Felsted Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left correction notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) receptacles shall be spaced such that no point along floor line is more than 6' from an outlet,334.30 nm cable shall not be stapled on edge, 314.20 in walls of combustible material, boxes shall be flush with the finished surface
ELE06-02073 Electrical Rough-In12/17/200712/18/200712/18/2007 8:53:08 AMAPASS
brian Phone #: ###-#### ric ok in garage for hot water heater and furnace only.
ELE07-04113 Rough-In Permanent Service12/17/200712/18/200712/18/2007 8:23:55 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, p/s, u/g, n, ok
ELE07-04113 Rough-In Permanent Service12/17/200712/18/200712/17/2007 11:48:00 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Alan Lusk Inspection cancelled from web by: Alan Lusk