Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03318 FIRE-Final Inspection12/18/200712/18/200712/18/2007 3:34:25 PMPPART
Life safety inspection passed, final pending shell and core permit final.
BLD06-03317 FIRE-Final Inspection12/18/200712/18/200712/18/2007 3:33:33 PMPPART
Final pending shell BLD permit.
BLD06-03322 FIRE-Final Inspection12/18/200712/18/200712/18/2007 3:31:37 PMPPART
Inspection passed pending repair of the striker at the front door latch, final pending shell BLD permit.
FIR07-00305 INSP-Final Inspection12/18/200712/18/200712/18/2007 3:27:57 PMPFAIL
2nd floor damper needs adjustment to enable complete and reliable closure.
FIR07-00922 INSP-Final Inspection12/18/200712/18/200712/18/2007 2:02:30 PMPPASS
Fire sprinkler system modifications passed inspection, ceiling tiles at the office area to be re-installed today, permit finaled.
FIR07-00733 INSP-Final Inspection12/18/200712/18/200712/18/2007 2:00:47 PMPPASS
Fire sprinkler work completed satisfactory, noted SW heads of the type installed to be provided at the riser head box as discussed.
FIR07-00976 INSP-Sprinkler Rough-in/Hydro12/18/200712/18/200712/18/2007 1:58:02 PMPPART
UG fire supply line hydrostatic test passed.
FIR06-00838 INSP-Final Inspection12/17/200712/18/200712/18/2007 12:17:35 PMPNR
According to project history, the underground supply has not yet been witnessed for flushing as required. Per phone conversation, contractor is not prepared to complete flushing today and will reschedule for tomorrow.
BLD07-00052 FIRE-Final Inspection12/17/200712/18/200712/18/2007 12:02:54 PMAFAIL
A fire alarm permit will be required for alteration and extension of the existing building FA system to include notification within this tenant remodel-see fire code review comments and notes attatched to the approved plan set, also noted the scope of work as indicated is not complete- missing walls, doors and finishes at several locations particularly on the west side of the corridor.
FIR07-00714 INSP-Final Inspection12/18/200712/18/200712/18/2007 11:55:34 AMAPASS
Fire alarm modification passed field inspection, permit finaled.
FIR07-01001 INSP-Final Inspection12/17/200712/18/200712/18/2007 11:35:05 AMAPASS
Inspection passed, fire sprinkler permit finaled.
FIR07-00669 FIR-Aging Inspection12/18/200712/18/200712/18/2007 10:00:36 AM DEFR
Work in progress. Pending field inspection request.
FIR07-00450 INSP-Alarm Testing12/12/200712/18/200712/18/2007 12:00:00 AMPCANC
bill Phone #: ###-####