Inspections for the day of: Tuesday, December 18, 2007.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00011 INSP-Alarm Testing12/18/200712/18/200712/18/2007 4:37:22 PMPDONE
The remaining fire alarm devices on the eighth floor have been tested. The smoke guard door for elevator three needs repaired.
FIR07-00816 INSP-Final Inspection12/17/200712/18/200712/18/2007 12:20:08 PMAFAIL
Provide forward flush to prove the new and high required flow for the additional sprinkler system and provide a retainging strap for the sprinkler line under the north overhead door.
FIR07-00881 INSP-Final Inspection12/14/200712/18/200712/18/2007 11:12:02 AMAFAIL
Three doors failed to latch when released by the fire alarm system. When these doors are retested and they latch this permit will be ok to final.
BLD07-02969 FIRE-Final Inspection12/17/200712/18/200712/18/2007 9:52:44 AMAFAIL
The fire alarm permit has not been issued but the contractor stated that the work has been done. I contacted mike timmerman about double fees. So no inspection was performed.
BLD07-02969 FIRE-Final Inspection12/18/200712/18/200712/18/2007 12:00:00 AMPPASS
Inspection completed by Ray Criner. At request of Dave Hanneman.
FIR07-01009 INSP-Final Inspection12/18/200712/18/200712/18/2007 12:00:00 AMPPASS
Factory installed suppresion system in new stand alone electric potato chip deep fryer appliance.Final inspection by Ray Criner.At request of Dave Hanneman.
FIR07-01017 INSP-Final Inspection12/18/200712/18/200712/18/2007 12:00:00 AMPPASS
Final inspection completed by Ray Criner At the request of Dave Hanneman..