Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02710 ELE-Aging Inspection12/18/201212/18/201212/20/2012 2:25:45 PM DONE
Drove by and was able to final
ELE11-02762 ELE-Aging Inspection12/18/201212/18/201212/20/2012 9:29:54 AM DONE
Contractor will call to schedule
ELE12-02932 Temporary Service12/17/201212/18/201212/18/2012 6:41:36 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Joe Thomas. T/S connect ok.
ELE12-02933 Temporary Service12/17/201212/18/201212/18/2012 4:46:18 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Joe Thomas t/s u/g n ok
ELE12-02965 Electrical Rough-In12/18/201212/18/201212/18/2012 4:07:58 PMPPASS
Floor heat in master bath. Please call to setup a time to gain entrance. Phone #: ###-#### >> Inspection requested via web by Eric Brown Floor heat rough in ok cover
ELE12-02522 Electrical Rough-In12/18/201212/18/201212/18/2012 3:39:45 PMPPASS
Please provide a rough-in inspection of the walls. Thank you! Phone #: ###-#### >> Inspection requested via web by Kevin Perez Wall rough in ok cover
ELE12-02786 Final12/18/201212/18/201212/18/2012 3:22:27 PMPNR
Please call Kyle with questions @ ###-####. Phone #: ###-#### >> Inspection requested via web by Amie Rose Piece of equiptment on floor with cover removed and electrical exposed.
GCE12-00188 GCE-Final12/18/201212/18/201212/18/2012 2:48:19 PMANH
(Mandatory Inspection) No access and no phone number associated with permit listed. Can not request hook up unless 36" work space is proviided in front of meter base
GCE12-00189 GCE-Rough-In12/18/201212/18/201212/18/2012 2:25:53 PMAPASS
Rough in ok cover p/s u/g n ok
ELE12-02990 Electrical Rough-In12/18/201212/18/201212/18/2012 1:50:48 PMPCANC
ron Phone #: ###-#### Needed rough in permanant service
ELE12-02990 Rough-In Permanent Service12/18/201212/18/201212/18/2012 1:50:19 PMPPASS
ron Phone #: ###-#### Rough in ok cover p/s o/h rec ok
ELE12-03054 Conference12/18/201212/18/201212/18/2012 12:55:40 PMPFAIL
MITCH Phone #: ###-#### Work performed without permit. Service- NEC 230.70 A service disconnect shall be located where service entrance conducors enter building.
Service grounding- NEC article 250. I can not verify the electrical service grounding and bonding.
Interior of building has too many violations to list-
a few are- open splices through out attic.
Overcurrent devices not properly sized.
Over current devices not list for panel.
All light fixtures and exit signs shall be hung from a 2 hour fire rated box and be grounded
ELE12-02982 Conference12/17/201212/18/201212/18/2012 11:18:23 AMADONE
LONNY Phone #: ###-#### Discussed additional ground rods to be added to ensure adequate true ground because of moisture barrier under entire project. sources of ground are ground rods, ground ring as drawn, concrete encased, metal water supply, fire sprinkler supply, building steel.
ELE12-02596 Final12/17/201212/18/201212/18/2012 10:47:56 AMAPASS
Kory Peterson is the Journeyman Electrician on site. Contact # ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Final ok
ELE12-03057 Electrical Rough-In12/17/201212/18/201212/18/2012 10:20:46 AMAPASS
Contact Wayne ###-#### Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Bathroom rough in ok cover
ELE12-02581 Final12/17/201212/18/201212/18/2012 9:52:20 AMAFAIL
>> Inspection requested via web by brad williams 230.9(B)(C) Over head service conductors shall not attach with in 3' of window.
ELE12-02581 Permanent Service12/18/201212/18/201212/18/2012 9:39:32 AMPPASS
>> Inspection requested via web by brad williams Can not final until power swing is at least 3 feet away from windows p/s o/h rec ok
ELE12-01379 Final12/17/201212/18/201212/18/2012 9:22:17 AMAPASS
I will send the owners a text Message to let them Know You are going to inspect in the morning so someone will be there Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk Final ok
ELE12-02603 Final12/13/201212/18/201212/18/2012 9:07:32 AMAPASS
Please call Mariane when you are on your way. Any problems give me a call. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
ELE12-02723 Final12/17/201212/18/201212/18/2012 8:41:37 AMAPASS
final for bonus room. Home owner will be home till !!:30 am. Thank You and have a Great Christmas Phone #: ###-#### >> Inspection requested via web by Julie Schroder Final ok