ELE11-02710
| ELE-Aging Inspection | 12/18/2012 | 12/18/2012 | 12/20/2012 2:25:45 PM | | DONE |
|
|
Drove by and was able to final
|
ELE11-02762
| ELE-Aging Inspection | 12/18/2012 | 12/18/2012 | 12/20/2012 9:29:54 AM | | DONE |
|
|
Contractor will call to schedule
|
ELE12-02932
| Temporary Service | 12/17/2012 | 12/18/2012 | 12/18/2012 6:41:36 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Joe Thomas. T/S connect ok.
|
ELE12-02933
| Temporary Service | 12/17/2012 | 12/18/2012 | 12/18/2012 4:46:18 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Joe Thomas t/s u/g n ok
|
ELE12-02965
| Electrical Rough-In | 12/18/2012 | 12/18/2012 | 12/18/2012 4:07:58 PM | P | PASS |
|
|
Floor heat in master bath. Please call to setup a time to gain entrance. Phone #: ###-#### >> Inspection requested via web by Eric Brown Floor heat rough in ok cover
|
ELE12-02522
| Electrical Rough-In | 12/18/2012 | 12/18/2012 | 12/18/2012 3:39:45 PM | P | PASS |
|
|
Please provide a rough-in inspection of the walls. Thank you! Phone #: ###-#### >> Inspection requested via web by Kevin Perez Wall rough in ok cover
|
ELE12-02786
| Final | 12/18/2012 | 12/18/2012 | 12/18/2012 3:22:27 PM | P | NR |
|
|
Please call Kyle with questions @ ###-####. Phone #: ###-#### >> Inspection requested via web by Amie Rose Piece of equiptment on floor with cover removed and electrical exposed.
|
GCE12-00188
| GCE-Final | 12/18/2012 | 12/18/2012 | 12/18/2012 2:48:19 PM | A | NH |
|
|
(Mandatory Inspection) No access and no phone number associated with permit listed. Can not request hook up unless 36" work space is proviided in front of meter base
|
GCE12-00189
| GCE-Rough-In | 12/18/2012 | 12/18/2012 | 12/18/2012 2:25:53 PM | A | PASS |
|
|
Rough in ok cover p/s u/g n ok
|
ELE12-02990
| Electrical Rough-In | 12/18/2012 | 12/18/2012 | 12/18/2012 1:50:48 PM | P | CANC |
|
|
ron Phone #: ###-#### Needed rough in permanant service
|
ELE12-02990
| Rough-In Permanent Service | 12/18/2012 | 12/18/2012 | 12/18/2012 1:50:19 PM | P | PASS |
|
|
ron Phone #: ###-#### Rough in ok cover p/s o/h rec ok
|
ELE12-03054
| Conference | 12/18/2012 | 12/18/2012 | 12/18/2012 12:55:40 PM | P | FAIL |
|
|
MITCH Phone #: ###-#### Work performed without permit. Service- NEC 230.70 A service disconnect shall be located where service entrance conducors enter building. Service grounding- NEC article 250. I can not verify the electrical service grounding and bonding. Interior of building has too many violations to list- a few are- open splices through out attic. Overcurrent devices not properly sized. Over current devices not list for panel. All light fixtures and exit signs shall be hung from a 2 hour fire rated box and be grounded
|
ELE12-02982
| Conference | 12/17/2012 | 12/18/2012 | 12/18/2012 11:18:23 AM | A | DONE |
|
|
LONNY Phone #: ###-#### Discussed additional ground rods to be added to ensure adequate true ground because of moisture barrier under entire project. sources of ground are ground rods, ground ring as drawn, concrete encased, metal water supply, fire sprinkler supply, building steel.
|
ELE12-02596
| Final | 12/17/2012 | 12/18/2012 | 12/18/2012 10:47:56 AM | A | PASS |
|
|
Kory Peterson is the Journeyman Electrician on site. Contact # ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Final ok
|
ELE12-03057
| Electrical Rough-In | 12/17/2012 | 12/18/2012 | 12/18/2012 10:20:46 AM | A | PASS |
|
|
Contact Wayne ###-#### Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Bathroom rough in ok cover
|
ELE12-02581
| Final | 12/17/2012 | 12/18/2012 | 12/18/2012 9:52:20 AM | A | FAIL |
|
|
>> Inspection requested via web by brad williams 230.9(B)(C) Over head service conductors shall not attach with in 3' of window.
|
ELE12-02581
| Permanent Service | 12/18/2012 | 12/18/2012 | 12/18/2012 9:39:32 AM | P | PASS |
|
|
>> Inspection requested via web by brad williams Can not final until power swing is at least 3 feet away from windows p/s o/h rec ok
|
ELE12-01379
| Final | 12/17/2012 | 12/18/2012 | 12/18/2012 9:22:17 AM | A | PASS |
|
|
I will send the owners a text Message to let them Know You are going to inspect in the morning so someone will be there Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk Final ok
|
ELE12-02603
| Final | 12/13/2012 | 12/18/2012 | 12/18/2012 9:07:32 AM | A | PASS |
|
|
Please call Mariane when you are on your way. Any problems give me a call. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
|
ELE12-02723
| Final | 12/17/2012 | 12/18/2012 | 12/18/2012 8:41:37 AM | A | PASS |
|
|
final for bonus room. Home owner will be home till !!:30 am. Thank You and have a Great Christmas Phone #: ###-#### >> Inspection requested via web by Julie Schroder Final ok
|