Inspections for the day of: Wednesday, December 18, 2013.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-02930 FIRE-Final Inspection12/17/201312/18/201312/18/2013 2:52:28 PMPFAIL
Provide current inspection and mount the fire extinguishers, repair existing exit signs and emergency lights, repair and test the roll down fire door, provide additional exit sign at the door as marked on the city approved plans.
FIR13-00519 INSP-Final Inspection12/16/201312/18/201312/18/2013 12:14:22 PMAFAIL
NAC circuit 1 has a "open" trouble, there is only one phone line, multiple strobes are overspaced, one strobe is blocked by movable partitions, I need verification that the strobes in the prep rooms are weatherproof and the remote annunciator (located outside) is weather proof, pull station in the crematorium is mounted too high. We did not set off the strobes to check sync. or test any devices since there was a trouble on the system and only one phone line.
BLD13-03371 FIRE-Final Inspection12/17/201312/18/201312/18/2013 12:02:14 PMAPASS
Life safety passed
BLD13-02023 FIRE-Final Inspection12/17/201312/18/201312/18/2013 10:14:02 AMAPASS
life safety passed
BLD13-01324 FIRE-Final Inspection12/17/201312/18/201312/18/2013 10:13:24 AMAPASS
Life safety passed