BLD13-02930
| FIRE-Final Inspection | 12/17/2013 | 12/18/2013 | 12/18/2013 2:52:28 PM | P | FAIL |
|
|
Provide current inspection and mount the fire extinguishers, repair existing exit signs and emergency lights, repair and test the roll down fire door, provide additional exit sign at the door as marked on the city approved plans.
|
FIR13-00519
| INSP-Final Inspection | 12/16/2013 | 12/18/2013 | 12/18/2013 12:14:22 PM | A | FAIL |
|
|
NAC circuit 1 has a "open" trouble, there is only one phone line, multiple strobes are overspaced, one strobe is blocked by movable partitions, I need verification that the strobes in the prep rooms are weatherproof and the remote annunciator (located outside) is weather proof, pull station in the crematorium is mounted too high. We did not set off the strobes to check sync. or test any devices since there was a trouble on the system and only one phone line.
|
BLD13-03371
| FIRE-Final Inspection | 12/17/2013 | 12/18/2013 | 12/18/2013 12:02:14 PM | A | PASS |
|
|
Life safety passed
|
BLD13-02023
| FIRE-Final Inspection | 12/17/2013 | 12/18/2013 | 12/18/2013 10:14:02 AM | A | PASS |
|
|
life safety passed
|
BLD13-01324
| FIRE-Final Inspection | 12/17/2013 | 12/18/2013 | 12/18/2013 10:13:24 AM | A | PASS |
|
|
Life safety passed
|