Inspections for the day of: Thursday, December 18, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02548 ELE-Aging Inspection12/18/201412/18/201412/19/2014 4:14:53 PM DONE
Waiting on contractor
ELE14-02431 Final12/18/201412/18/201412/18/2014 3:29:21 PMPPASS
Contact: Wes Powell Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
ELE14-01595 Final12/18/201412/18/201412/18/2014 3:27:39 PMPPASS
Final ok
ELE14-03471 Temporary Service12/18/201412/18/201412/18/2014 2:07:59 PMPPASS
Phone #: ###-#### Inspection requested via web by JENNY EMEL t/s u/g n ok
ELE14-02585 Final12/18/201412/18/201412/18/2014 1:44:46 PMPPASS
please contact james at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
ELE14-03455 Rough-In Permanent Service12/17/201412/18/201412/18/2014 12:34:45 PMAFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
300.4(B)- Listed bushings shall be installed in holes in metal side of furnace.
334.30- NM cable shall be secured within 12" of boxes.
320.23- Cables shall be protected with in 7' of attic access.
314.17- NM cable sheathing shall enter box knock out a minimum of 1/4".
Temporary receptical outlets need installed. Can't approve a service with stripped wires hanging out of boxes.
ELE14-02945 Final12/17/201412/18/201412/18/2014 10:05:58 AMAPASS
Please call Perry (###-####) 30 minutes ahead for access Phone #: ###-#### Inspection requested via web by Brad Girard Final ok
ELE14-02919 Final12/17/201412/18/201412/18/2014 9:29:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
ELE14-03239 Electrical Rough-In12/17/201412/18/201412/18/2014 9:00:05 AMAPASS
Lower portion of the pump station Phone #: ###-#### Inspection requested via web by Lori Stout Lower floor pour and electrical room floor, 4/0 copper under ground to well casing. Rough in ok cover
ELE14-03454 Rough-In Permanent Service12/17/201412/18/201412/18/2014 8:36:03 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
ELE13-00214 Final12/18/201412/18/201412/18/2014 8:08:37 AMPFAIL
400.8(4)- Flexible cords uses not permitted. Where attached to building structures. Open sign on North side of buiding.