FIR13-00725
| INSP-Sprinkler Rough-in | 12/17/2014 | 12/18/2014 | 12/18/2014 4:42:55 PM | P | PART |
|
|
Completed rough-in inspection at the 4th floor plan sheet FP17. Items noted include; obstructed ECU at the filing room, missing coverage at a closet not shown on plan adjacent to a storage room, overspaced ECU at two locations within the heilix, provide pendent at new drop ceiling formerly OTS, relocate upright sprinkler at the center storage room A23 to meet design spacing. Locations marked on plan set.
|
FIR14-00883
| INSP-Final Inspection | 12/18/2014 | 12/18/2014 | 12/18/2014 4:30:18 PM | P | DEFR |
|
|
Phone #: ###-#### Inspection requested via web by Don Kartchner *Inspection request intended for 12/19 per contractor*
|
BLD14-01641
| FIRE-Final Inspection | 12/18/2014 | 12/18/2014 | 12/18/2014 4:24:42 PM | P | PASS |
|
|
C/N items verified. Life safety finaled.
|
FIR14-00311
| INSP-Final Inspection | 12/18/2014 | 12/18/2014 | 12/18/2014 4:21:43 PM | P | PASS |
|
|
Scope of work completed. Inspection passed, permit finaled.
|
FIR14-00862
| INSP-Final Inspection | 12/18/2014 | 12/18/2014 | 12/18/2014 1:10:33 PM | P | PEND |
|
|
RTU not yet installed to facilitate completion of fire alarm permit work. Okayed for temp occ per agreement.
|
FIR14-00624
| INSP-Sprinkler Rough-in/Hydro | 12/18/2014 | 12/18/2014 | 12/18/2014 11:56:18 AM | A | PART |
|
|
Rough-in and tenting inspections passed. Verified heating to be provided at the shop room adjacent to the garage. Plan mod okayed.
|
FIR14-00877
| INSP-Final Inspection | 12/17/2014 | 12/18/2014 | 12/18/2014 10:09:37 AM | A | CANC |
|
|
Final AES Install Phone #: ###-#### >> Inspection requested via web by Jeremy Berg Inspection cancelled from web by: Jeremy Berg
|