FIR14-00474
| INSP-Final Inspection | 12/17/2014 | 12/18/2014 | 12/19/2014 2:36:51 PM | A | CANC |
|
|
Bernie, the general contractor, wanted life safety a priority so sprinkler inspection is being canceled.
|
BLD14-01863
| FIRE-Final Inspection | 12/17/2014 | 12/18/2014 | 12/18/2014 3:36:06 PM | P | FAIL |
|
|
Went over life safety requirements with owner and general contractor. Need exit discharge lighting, Man Trap door operation approved, fire extinguishers verified, hydrant location verified, gate width verifed, emergency generator certification, need electrical room signs, battery room signs, riser room signage, fire dept access signage, need address, need project related fire alarm and fire sprinkler permits finaled.
|
FIR14-00421
| INSP-Sprinkler Rough-in/Hydro | 12/18/2014 | 12/18/2014 | 12/18/2014 3:30:55 PM | P | PASS |
|
|
Overhead hydro passed
|
FIR14-00578
| INSP-Sprinkler Rough-in/Hydro | 12/17/2014 | 12/18/2014 | 12/18/2014 1:50:39 PM | P | PASS |
|
|
The tenting and rough-in and hydro test for the overhead passed. Piping can be covered.
|
FIR14-00848
| INSP-Sprinkler Rough-in | 12/17/2014 | 12/18/2014 | 12/18/2014 11:28:35 AM | A | PASS |
|
|
underground supply line ok to cover
|
FIR14-00398
| INSP-Sprinkler Rough-in/Hydro | 12/17/2014 | 12/18/2014 | 12/18/2014 11:27:50 AM | A | PASS |
|
|
Overhead hydro test passed
|
FIR14-00397
| INSP-Sprinkler Rough-in/Hydro | 12/17/2014 | 12/18/2014 | 12/18/2014 11:27:31 AM | A | PASS |
|
|
Overhead hydro test passed
|
BLD14-02226
| FIRE-Final Inspection | 12/17/2014 | 12/18/2014 | 12/18/2014 9:23:13 AM | A | PASS |
|
|
life safety passed
|