ELE15-02697
| Electrical Rough-In | 12/17/2015 | 12/18/2015 | 12/18/2015 1:33:52 PM | A | PASS |
|
|
Phase 3 units. Please contact Jerry ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough-in ok cover East and West stairwells, 2nd floor corridor, Rooms 101,102,103,104,105 & 201,202,203,204,205
|
ELE15-03877
| Final | 12/17/2015 | 12/18/2015 | 12/18/2015 10:41:53 AM | A | FAIL |
|
|
Home owner will be home form 9-1 on Friday. Phone #: ###-#### Inspection requested via web by Clint Tate NEC 210.52C(3) Peninsular countertop spaces, At least one receptacle shall be installed at each peninsular countertop spacewith a long dimension of 24in or greater, within 12in. of countertop
|
ELE15-03332
| Electrical Rough-In | 12/17/2015 | 12/18/2015 | 12/18/2015 10:05:57 AM | A | PASS |
|
|
We need a light pole base inspection please. Thank you. Phone #: ###-#### Inspection requested via web by Thomas Jenkins rough-in ok cover west 4 pole bases
|
ELE15-02908
| Electrical Rough-In | 12/17/2015 | 12/18/2015 | 12/18/2015 9:36:28 AM | A | PASS |
|
|
We are requesting a wall rough-in inspection for tomorrow 12/18/15 in the AM. Our contact is Rod ###-####, Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate rough-in ok cover walls
|
ELE15-03544
| Electrical Rough-In | 12/16/2015 | 12/18/2015 | 12/18/2015 9:10:43 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Craig Korell NEC 300.4 Nail plates where bored holes for MC are within 1 1/4 of edge of framing member. NEC 330.12 MC shall not be installed where subject to phyical damage, 1 1/4 from edge of framing member. NEC 330.30 MC shall be secured within 12 in. of every box, cabnet. NEC 358.30 EMT shall be secured within 3 ft. of every box, cabnet.
|
ELE15-03758
| Temporary Service | 12/17/2015 | 12/18/2015 | 12/17/2015 3:12:41 PM | A | PASS |
|
|
See Darryl for any clarification on this inspection. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot t/s o/h n ok
|