Inspections for the day of: Monday, December 18, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03415 ELE-Aging Inspection12/18/201712/18/201712/26/2017 2:34:51 PM PASS
Drove by and inspected.
ELE17-02649 Electrical Rough-In12/15/201712/18/201712/18/2017 3:03:31 PMPPASS
contact is Andy Chambers Phone #: ###-#### Inspection requested via web by Scott Campbell
Discussed required work clearence for control panels on VAV units located above grid. Minimum of 18" deep and 24" wide as per Daryl DeGrange for tight spaces. Other areas shall have full required by voltage present.
3 more extended stay rooms and janitors closet as noted on contractor print. Wall rough in ok cover
ELE17-02310 Final12/18/201712/18/201712/18/2017 2:07:48 PMPFAIL
Homeowner will be available 2 walkthrough. Phone #: ###-#### Inspection requested via web by Casey Fouts
210.8- All garage 120 volt receptacles shall have GFCI protection. Garage refrigerator.
406.6- Old receptacle in brick in craft room is a grounded type receptacle on a ungrounded circuit. Blank, change to 2 wire receptacle or GFCI protect grounding type receptacle. No code violation shall be retained.
408.4- Circuit directory shall be complete on sub panel and service panel.
ELE17-03026 Final12/14/201712/18/201712/18/2017 12:47:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE17-02732 Final12/14/201712/18/201712/18/2017 12:47:06 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
210.8(B)- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Mother's room.
314.25- Furniture outlets and covers shall be install. If outlets are not being used on furniture blanks shall be installed due to live spade connectors exposed.
See RI for IT room ceiling violations.
ELE17-02732 Electrical Rough-In12/14/201712/18/201712/18/2017 12:41:06 PMAFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
314.29- Access shall be provided for electrical boxes. HVAC equipment above grid blocks access panel for existing elevator shaft acess which has electrical located in it. Minimum of 90 degrees for door swing shall be provided.
400.12- Flexible cords shall not be run above or pass thru grid. Receptacle has been relocated however pump has not which has flexible cord.
ELE17-01536 Permanent Service12/15/201712/18/201712/18/2017 9:54:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Training and safety building. 9,500 Available fault current. p/s u/g n ok
ELE17-01537 Permanent Service12/15/201712/18/201712/18/2017 9:53:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Admin classroom building. 9,500 Available fault current. p/s u/g n ok
ELE17-04230 Rough-In Permanent Service12/16/201712/18/201712/18/2017 9:12:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Murray
Rough in ok cover p/s u/g n ok
ELE17-04057 Electrical Rough-In12/17/201712/18/201712/18/2017 8:33:13 AMAPASS
call one half hour before inspection to ensure building is unlocked Phone #: ###-#### Inspection requested via web by Steve Craig
Wall rough in ok cover