Inspections for the day of: Monday, December 18, 2017.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-04159 Conference12/15/201712/18/201712/18/2017 3:07:18 PMPDONE
Matt Phone #: ###-#### Discussed outlet layout in kitchen re-model. Walls are open, new outlet layout must conform to current code requirements. Outlets installed within 2 feet of edge of countertop and every 4 there after. Also within 2 feet on both sides of the sink. There was an existing 12/2 at end of peninsula that was not being used.
ELE16-03965 Final12/18/201712/18/201712/18/2017 2:40:24 PMPPASS
Call with questions - Rocky Phone #: ###-#### Ok final.
ELE17-04140 Rough-In Permanent Service12/18/201712/18/201712/18/2017 2:11:02 PMPPASS
Phone #: ###-#### Inspection requested via web by Jay Hutchison p/s u/g n ok
ELE17-02390 Final12/15/201712/18/201712/18/2017 1:53:33 PMPCANC
Building D Final Phone #: ###-#### Inspection requested via web by Bob Stephens Scheduled for 12/19/17
ELE17-02918 Final12/18/201712/18/201712/18/2017 1:32:03 PMPPASS
Rocky Phone #: ###-#### Ok final. Power from control cabinet run to ceiling hung basketball hoops that plug in. Used for raising and lowering.
ELE17-04222 Permanent Service12/15/201712/18/201712/18/2017 1:09:46 PMPPASS
call Patrick with questions Phone #: ###-#### Inspection requested via web by A.M.E. Office p/s o/h n ok
ELE17-02959 Electrical Rough-In12/15/201712/18/201712/18/2017 1:09:25 PMPPASS
Underground inspection for feeders Phone #: ###-#### Inspection requested via web by Kevin Perez Ok cover 2 " pvc from transformer to building.
ELE17-01682 Final12/18/201712/18/201712/18/2017 12:53:36 PMPNR
Glen Phone #: ###-####
1. Tamper and Weather resistant recepts needed for outside.
2. Weather proof in use covers needed for outside 2 locations.
3. Tamper resistant required in garage and upstairs pottery area.
ELE17-03902 Final12/15/201712/18/201712/18/2017 12:10:37 PMAPASS
Phone #: ###-#### Inspection requested via web by Mike Leonard Ok final. Disconnect located on pole with service.
ELE17-03902 Electrical Rough-In12/18/201712/18/201712/18/2017 12:10:02 PMPPASS
Met contractor on-site. All components UL listed.
ELE17-02888 Final12/17/201712/18/201712/18/2017 11:31:50 AMAPASS
Please call before to get access code. Phone #: ###-#### Inspection requested via web by Spencer McLean Ok final. Load served with 2 pole 30. Grounding electrode conductor attached to building steel on rooftop.
ELE17-04233 Temporary Service12/18/201712/18/201712/18/2017 9:51:49 AMAPASS
Phone #: ###-#### Inspection requested via web by Shaun Kirkman t/s u/g n ok
ELE17-03819 Final12/14/201712/18/201712/18/2017 9:16:41 AMAPASS
Carlos or ###-#### Phone #: ###-####
ELE17-03996 Rough-In Permanent Service12/15/201712/18/201712/18/2017 9:00:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Eric Brown p/s u/g n ok. Flex 90 in back of 4 sq box N wall kitchen. Talked to electrician, he is going to be up there this morning to change it.