Inspections for the day of: Monday, December 18, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00326 INSP-Sprinkler Rough-in/Hydro12/18/201712/18/201712/18/2017 12:15:29 PMPPASS
Overhead hydro test passed

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00321 INSP-Sprinkler Rough-in12/18/201712/18/201712/18/2017 12:15:07 PMPPASS
Overhead hydro test passed

Phone #: ###-#### Inspection requested via web by Sam Ball
GRD17-00059 FIRE-Final Inspection12/18/201712/18/201712/18/2017 12:14:40 PMPPASS
Life safety passed

Jeff Phone #: ###-####
FIR17-00321 INSP-Supply line flush12/18/201712/18/201712/18/2017 12:01:43 PMPPASS
Underground supply line flush passed

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-00448 FIRE-Final Inspection12/18/201712/18/201712/18/2017 12:00:44 PMPCANC
No life safety sign off required.

Marty Phone #: ###-####
GRD16-00071 FIRE-Final Inspection12/18/201712/18/201712/18/2017 11:54:33 AMPPASS
Life safety passed. Per Scott Arellano since the plans have been misplaced the fire dept access and the two fire hydrants could be verified from the civil sheets of the project approved building permit plans.
GRD16-00071 FIRE-Final Inspection12/17/201712/18/201712/18/2017 11:54:14 AMAPASS
Life safety passed. Per Scott Arellano since the plans have been misplaced the fire dept access and the two fire hydrants could be verified from the civil sheets of the project approved building permit plans.

Phone #: ###-#### Inspection requested via web by David Scaggs
BLD17-03163 FIRE-Final Inspection12/15/201712/18/201712/18/2017 11:41:42 AMAPASS
Life safety passed

Phone #: 3102188097 >> Inspection requested via mobile web by Jeff ratlief
FIR17-00665 INSP-Final Inspection12/15/201712/18/201712/18/2017 9:50:23 AMAPASS
Permit finaled
FIR17-00499 INSP-Sprinkler Rough-in12/15/201712/18/201712/18/2017 9:24:06 AMAPASS
Rough-in complete in Rooms 209 and 210. Piping can be covered.
BLD14-02837 FIRE-Final Inspection12/15/201712/18/201712/18/2017 12:00:00 AMACANC
Please call ahead for access - Lee Phone #: ###-####