Inspections for the day of: Wednesday, December 18, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04826 Electrical Rough-In12/17/201912/18/201912/18/2019 2:17:31 PMPCANC
We need a uffer inspection please. Thank you. Phone #: ###-#### Inspection requested via web by Tom Jenkins...contractor notified rebar did not get installed...inspection scheduled for next day
ELE19-04706 Electrical Rough-In12/18/201912/18/201912/18/2019 2:11:41 PMPPASS
rough in for all stairway breezeway ceilings for light whips into drop ceiling.
rough in for sub panel feeders up East side of building and across breezeways. Phone #: ###-#### Inspection requested via web by Todd Hall...

rough ok to cover listed areas
ELE19-04706 Permanent Service12/18/201912/18/201912/18/2019 2:10:44 PMPNR
service on East side of building Phone #: ###-#### Inspection requested via web by Todd Hall...not complete...will reschedule...sub feeds need landed in unit panels
ELE19-04850 Final12/18/201912/18/201912/18/2019 12:25:20 PMPFAIL
Jay Phone #: ###-####...
1) not ready for final...inspection needs to be permanent service - final once power is on at building
2) unable to verify grounding for service
uffer ground? ground rods?
3) riser needs strapped to manufacturers instructions and within 3ft of meter/panel
4) required bonding of building unverifiable
individual steel containers
5) no code violation shall be retained - exposed NMB cable on exterior of building...missing front light
ELE19-04853 Final12/18/201912/18/201912/18/2019 11:26:54 AMPFAIL
Inspection so that they can turn power back on to a building that has been without power for over a year per Idaho Power''s request. Phone #: ###-#### Inspection requested via web by Seth Stears...
1...access to electrical rm is required to verify/inspect panels
2..AFC label is required to energize service
3..required grounding of service-unable to verify

recommend contractor meet for inspection being a carwash


ELE19-04625 Final12/18/201912/18/201912/18/2019 10:43:19 AMPPASS
Contact: Jason Noble Phone #: ###-#### Inspection requested via web by Deb Gooden...
see rough inspection notes...pipes only...ok to final
ELE19-03519 Final12/12/201912/18/201912/18/2019 10:40:54 AMAPASS
electrician not onsite. can call office for details. Phone #: ###-#### Inspection requested via web by Matthew White...ok to final
ELE19-04808 Final12/17/201912/18/201912/18/2019 10:23:12 AMAPASS
For access to the store please call Scott ###-#### 1/2 prior to arrival. Rigo is the contact for RME ###-#### Phone #: ###-#### Inspection requested via web by Buster Bowen..
power added off existing circuit...outside security door...ok to final
ELE19-02762 Final12/17/201912/18/201912/18/2019 10:05:46 AMAPASS
Charlie Phone #: ###-####..ok to final
ELE19-04789 Permanent Service12/13/201912/18/201912/18/2019 8:15:29 AMPCANC
Someone will be there. Call Fred with any questions at ###-#### Phone #: ###-#### >> Inspection requested via web by Clayton Morgan Inspection cancelled from web by: Clayton Morgan