Inspections for the day of: Monday, December 19, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01298 BLD-Aging Inspection12/19/200512/19/200512/23/2005 11:28:48 AMPDONE
Inspection scheduled for 12/27 per conversation with Jerry
BLD05-03254 FIRE-Final Inspection12/19/200512/19/200512/20/2005 9:41:29 AMPPASS
Life safety is satisfactory, inspection passed.
FIR05-00396 INSP-Sprinkler Rough-in12/16/200512/19/200512/19/2005 5:13:57 PMPDEFR
Wrong permit number called in, this inspection was for the related TI work on the second floor rough-in for cover.
BLD04-02808 FIRE-Final Inspection12/19/200512/19/200512/19/2005 3:43:25 PMPPART
Inspected apts. 512 and 510 1st and 2nd floors, fire ext. are okay, smoke detectors at two locations on the 2nd floor apt. 510 are below 12" from the ceiling on the wall, relocate as discussed.
BLD05-02802 FIRE-Final Inspection12/19/200512/19/200512/19/2005 2:47:30 PMPPASS
Correction items have been completed per Jim Storey, fire life safety passed inspecton.
FIR05-00734 INSP-Final Inspection12/16/200512/19/200512/19/2005 2:45:22 PMPCANC
No additional time available for this inspection to be completed today due to related fire alarm permit inspections performed at this same location.
FIR05-00735 INSP-Final Inspection12/16/200512/19/200512/19/2005 2:43:56 PMPPASS
Fire alarm passed inspection for the third floor TI space.
FIR05-00169 INSP-Final Inspection12/16/200512/19/200512/19/2005 2:41:42 PMPPASS
Items on correction notice have been completed, alarm tested satisfactory, permit finaled.
FIR05-00760 INSP-Sprinkler Rough-in/Hydro12/19/200512/19/200512/19/2005 11:53:12 AMPCANC
Wrong permit called in, the inspection under the correct related permit to be performed tomorrow as agreed.
FIR05-00190 INSP-Sprinkler Rough-in/Hydro12/19/200512/19/200512/19/2005 11:49:25 AMPPART
Overhead rough-in is good for cover at four hard lid areas as marked on approved plans.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro12/16/200512/19/200512/19/2005 11:08:54 AMAFAIL
See approved plans for areas defficient including spacing, non-listed valves, coated heads, seismic bracing, signs, missing inspectors test, hanger issues, and areas not inspected at this time-todays inspection was for rough-in at 2nd, 3rd, 4th, floors parking garage dry systems and 1st floor 6" main in soffit. 6" main in the 1st floor soffit is okay to cover except at one lateral brace next to mech. room.