BLD04-01298
| BLD-Aging Inspection | 12/19/2005 | 12/19/2005 | 12/23/2005 11:28:48 AM | P | DONE |
|
|
Inspection scheduled for 12/27 per conversation with Jerry
|
BLD05-03254
| FIRE-Final Inspection | 12/19/2005 | 12/19/2005 | 12/20/2005 9:41:29 AM | P | PASS |
|
|
Life safety is satisfactory, inspection passed.
|
FIR05-00396
| INSP-Sprinkler Rough-in | 12/16/2005 | 12/19/2005 | 12/19/2005 5:13:57 PM | P | DEFR |
|
|
Wrong permit number called in, this inspection was for the related TI work on the second floor rough-in for cover.
|
BLD04-02808
| FIRE-Final Inspection | 12/19/2005 | 12/19/2005 | 12/19/2005 3:43:25 PM | P | PART |
|
|
Inspected apts. 512 and 510 1st and 2nd floors, fire ext. are okay, smoke detectors at two locations on the 2nd floor apt. 510 are below 12" from the ceiling on the wall, relocate as discussed.
|
BLD05-02802
| FIRE-Final Inspection | 12/19/2005 | 12/19/2005 | 12/19/2005 2:47:30 PM | P | PASS |
|
|
Correction items have been completed per Jim Storey, fire life safety passed inspecton.
|
FIR05-00734
| INSP-Final Inspection | 12/16/2005 | 12/19/2005 | 12/19/2005 2:45:22 PM | P | CANC |
|
|
No additional time available for this inspection to be completed today due to related fire alarm permit inspections performed at this same location.
|
FIR05-00735
| INSP-Final Inspection | 12/16/2005 | 12/19/2005 | 12/19/2005 2:43:56 PM | P | PASS |
|
|
Fire alarm passed inspection for the third floor TI space.
|
FIR05-00169
| INSP-Final Inspection | 12/16/2005 | 12/19/2005 | 12/19/2005 2:41:42 PM | P | PASS |
|
|
Items on correction notice have been completed, alarm tested satisfactory, permit finaled.
|
FIR05-00760
| INSP-Sprinkler Rough-in/Hydro | 12/19/2005 | 12/19/2005 | 12/19/2005 11:53:12 AM | P | CANC |
|
|
Wrong permit called in, the inspection under the correct related permit to be performed tomorrow as agreed.
|
FIR05-00190
| INSP-Sprinkler Rough-in/Hydro | 12/19/2005 | 12/19/2005 | 12/19/2005 11:49:25 AM | P | PART |
|
|
Overhead rough-in is good for cover at four hard lid areas as marked on approved plans.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 12/16/2005 | 12/19/2005 | 12/19/2005 11:08:54 AM | A | FAIL |
|
|
See approved plans for areas defficient including spacing, non-listed valves, coated heads, seismic bracing, signs, missing inspectors test, hanger issues, and areas not inspected at this time-todays inspection was for rough-in at 2nd, 3rd, 4th, floors parking garage dry systems and 1st floor 6" main in soffit. 6" main in the 1st floor soffit is okay to cover except at one lateral brace next to mech. room.
|