Inspections for the day of: Tuesday, December 19, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00757 INSP-Final Inspection12/19/200612/19/200612/19/2006 5:03:52 PMPPASS
Fire alarm final inspection passed, permit finaled.
FIR06-00980 INSP-Sprinkler Rough-in12/18/200612/19/200612/19/2006 4:21:51 PMPPART
Overhead install is approved for cover at the drop ceiling areas for the permitted work scope.
BLD06-00769 FIRE-Final Inspection12/19/200612/19/200612/19/2006 4:05:43 PMPPASS
Final inspection for apt. 300, 301, 308, 309 is acceptable, fire extinguishers for these units are on site and are to be installed today as a condition of approval.
FIR05-00695 INSP-Final Inspection12/19/200612/19/200612/19/2006 3:15:41 PMPDEFR
No time available to perform this inspection today, rescheduled as discussed with contractor.
FIR06-00671 INSP-Sprinkler Rough-in12/14/200612/19/200612/19/2006 3:11:55 PMPDEFR
steve - 200 lb test ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith No time available to complete this inspection today, to be rescheduled per phone conversation with contractor as agreed.
FIR06-00444 INSP-Final Inspection12/19/200612/19/200612/19/2006 3:08:42 PMPPASS
UG fire supply line permit finaled.
FIR06-00496 INSP-Final Inspection12/19/200612/19/200612/19/2006 3:08:13 PMPPASS
Required corrections verified for completion, fire sprinkler permit finaled.
FIR05-00271 INSP-Sprinkler Rough-in12/18/200612/19/200612/19/2006 3:02:19 PMPCANC
No time available to complete this inspection today.
FIR06-00607 INSP-Final Inspection12/19/200612/19/200612/19/2006 3:01:05 PMPPASS
Final alarm inspection passed, permit finaled.
FIR06-00981 INSP-Final Inspection12/18/200612/19/200612/19/2006 2:59:09 PMPPASS
Fire alarm work tested satisfactory, permit finaled.
FIR06-00240 FIR-Aging Inspection12/19/200612/19/200612/19/2006 12:53:19 PM DONE
wip
FIR06-00898 INSP-Final Inspection12/18/200612/19/200612/19/2006 12:29:00 PMAPART
OH fire sprinkler install is good for cover at the drop ceiling areas within the TI space.
BLD06-02699 FIRE-Final Inspection12/18/200612/19/200612/19/2006 11:40:22 AMAFAIL
Provide building address numbers, manual flush bolts are not allowed at the main entry/exit pair of doors, door hardware at the mech. room is not approved, need provide testing for the two duct detectors.
FIR06-00717 INSP-Sprinkler Rough-in/Hydro12/18/200612/19/200612/19/2006 11:37:21 AMAFAIL
Arm-overs at drops must be supported within 1' and restrained against upward movement due to static pressures above 100psi., need to remove existing upright heads above the drop ceilings, one pendent head is obstructed at an exposed column.