FIR07-00691
| FIR-Aging Inspection | 12/19/2007 | 12/19/2007 | 12/27/2007 12:36:46 PM | | DEFR |
|
|
|
BLD07-01431
| FIRE-Alarm Testing | 12/18/2007 | 12/19/2007 | 12/20/2007 11:52:16 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR07-00884
| INSP-Sprinkler Rough-in | 12/17/2007 | 12/19/2007 | 12/19/2007 3:49:07 PM | A | PART |
|
|
OH fire sprinkler work is approved for cover at the drop ceiling areas.
|
FIR07-00877
| INSP-Final Inspection | 12/17/2007 | 12/19/2007 | 12/19/2007 3:43:01 PM | A | PASS |
|
|
Corrections completed, fire sprinkler permit finaled.
|
FIR06-00838
| INSP-Final Inspection | 12/18/2007 | 12/19/2007 | 12/19/2007 3:32:50 PM | P | FAIL |
|
|
No approved set of plans on site, will call this in for tomorrow to do under ground flush and final. KR
|
FIR07-00737
| INSP-Sprinkler Rough-in/Hydro | 12/19/2007 | 12/19/2007 | 12/19/2007 3:03:40 PM | P | PART |
|
|
OH hydrostatic test for the basement and 2nd floor wet systems passed inspection.
|
BLD07-03099
| FIRE-Final Inspection | 12/19/2007 | 12/19/2007 | 12/19/2007 2:44:08 PM | P | PASS |
|
|
Correction notice items are complete, life safety passed.
|
BLD07-02970
| FIRE-Final Inspection | 12/18/2007 | 12/19/2007 | 12/19/2007 2:26:55 PM | P | PASS |
|
|
Fire life safety is satisfactory, noted class K PFE to be provided as discussed, ceiling tiles repalaced where missing, and finishes completed prior to structural final inspection.
|
FIR07-01016
| INSP-Final Inspection | 12/19/2007 | 12/19/2007 | 12/19/2007 2:24:54 PM | P | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
FIR07-00937
| INSP-Sprinkler Rough-in/Hydro | 12/18/2007 | 12/19/2007 | 12/19/2007 2:24:11 PM | A | FAIL |
|
|
OH Hydrostatic test failed due to 25 psi. pressure loss at the guage.
|
BLD07-01877
| FIRE-Final Inspection | 12/18/2007 | 12/19/2007 | 12/19/2007 11:01:10 AM | A | NR |
|
|
Need project related fire alarm permit work inspected and finaled prior to BLD life safety approval.
|
FIR06-00838
| INSP-Final Inspection | 12/18/2007 | 12/19/2007 | 12/18/2007 2:36:19 PM | P | CANC |
|
|
Reschedule final, Brian F is the contact. Thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|