Inspections for the day of: Friday, December 19, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01416 DOC - Permit Expired12/19/200812/19/200812/19/2008 4:00:21 PMPPASS
no work done in over 1 year
ELE07-01415 DOC - Permit Expired12/19/200812/19/200812/19/2008 3:48:27 PMPPASS
no work done in over 1 year
ESC08-00987 General Inspection12/19/200812/19/200812/19/2008 3:33:26 PMPPASS
looks ok
ESC08-00989 General Inspection12/19/200812/19/200812/19/2008 3:33:10 PMPPASS
looks ok
ELE08-03259 Rough-In Permanent Service12/19/200812/19/200812/19/2008 3:32:48 PMPPASS
tom Phone #: ###-####
checl location of receps serving counter on final
R/I Ok
P/S U/G N Ok
ELE08-03258 Rough-In Permanent Service12/19/200812/19/200812/19/2008 3:07:44 PMPPASS
tom Phone #: ###-####
check for required recep for kitchen counter on final.
R/I Ok
P/S U/G N Ok
ELE08-02812 Final12/19/200812/19/200812/19/2008 2:35:39 PMPNH
Garage Code 1344 Phone #: ###-#### Internet Inspection Request from: Dan Rohl
door from garage was locked left notice and called dan
ESC08-00822 General Inspection12/19/200812/19/200812/19/2008 1:53:02 PMPPASS
looks ok
ESC08-00435 General Inspection12/19/200812/19/200812/19/2008 1:52:50 PMPPASS
looks ok
ELE08-02629 Permanent Service12/19/200812/19/200812/19/2008 1:52:30 PMPPASS
steve Phone #: ###-####
P/S U/g N Ok
ELE08-02168 Electrical Rough-In12/18/200812/19/200812/19/2008 1:33:02 PMPFAIL
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten
protect romex within 1 1/4" of framing members and also in attic crawl spaces install all necessary boxes. hand rail is wall space for 210.52. provide 6 in free conductor at all junction/splice points. mounting screws not permited inside of nm boxes. insure boxes are flush.
ELE08-02509 DOC - Permit Finaled12/19/200812/19/200812/19/2008 11:35:38 AMPPASS
ELE08-02795 Final12/19/200812/19/200812/19/2008 10:29:01 AMAPASS
CONTACT LARRY FINAL COMM INSP. Phone #: ###-#### Internet Inspection Request from: Emmet Bushman
ELE08-03235 Conference12/16/200812/19/200812/19/2008 9:32:13 AMAPART
Lars Phone #: ###-####
talked about bringing illeagle wiring up to code.