Inspections for the day of: Thursday, December 19, 2013.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00588 ELE-Aging Inspection12/19/201312/19/201312/20/2013 8:55:32 AM CANC
too busy
ELE11-02838 ELE-Aging Inspection12/19/201312/19/201312/20/2013 8:52:06 AM CANC
too busy
GCE13-00210 GCE-Final12/19/201312/19/201312/19/2013 7:53:39 PMPPASS
Jeff ###-#### Temp pole final ok
ELE13-02874 Final12/18/201312/19/201312/19/2013 7:50:58 PMPNR
Donald Phone #: ###-#### Junction boxes still being installed, Circuits cold and covers missing.
GCE13-00210 GCE-Temporary Service12/19/201312/19/201312/19/2013 3:40:02 PMPPASS
Jeff ###-#### t/s u/g n ok
ELE13-03492 Permanent Service12/16/201312/19/201312/19/2013 3:00:54 PMPPASS
200amp service upgrade, will be ready in afternoon, any questions please call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s o/h rec ok
ELE13-03492 Final12/19/201312/19/201312/19/2013 3:00:18 PMPPASS
200amp service upgrade, will be ready in afternoon, any questions please call Clint @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose Service final ok
ELE13-03049 Electrical Rough-In12/19/201312/19/201312/19/2013 2:33:37 PMPPASS
wall Cover. Dan on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen Cooler walls and front desk inside cover and up mezzining by phone board rough in ok cover
ELE13-02688 Electrical Rough-In12/19/201312/19/201312/19/2013 1:59:22 PMPPASS
Ceiling cover. Phone #: ###-#### >> Inspection requested via web by Buster Bowen
Hard lid rough in ok cover
ELE13-02623 Final12/19/201312/19/201312/19/2013 1:25:46 PMPPASS
MIKE PLEASE CALL 30? BEFORE Phone #: ###-#### Kitchen remodel final ok
ELE04-02374 Final12/18/201312/19/201312/19/2013 10:56:00 AMAFAIL
Before 11, call for access - April Phone #: ###-#### BCC-4-05-23 Unlawful to conceal. Basement wiring covered with out first being inspected.
210.52- Basement dows not have minimum reqired receptical outlet installed measured along floor line.
314.25- All boxes shall be complete with covers. Furnace disconnect.
422.30- A disconnecting means shall be provided for water heater.
110.3- Family room receptical outlet not working.
210.8- Back outdoor receptical shall have GFCI protection.
406.3(D)- Grounding type recepticals installed on non-grounded circuits shall have GFCI protection.
GCE13-00209 GCE-Final12/18/201312/19/201312/19/2013 9:54:22 AMAPASS
Dominic ###-#### Service final ok
GCE13-00209 GCE-Permanent Service12/19/201312/19/201312/19/2013 9:53:37 AMPPASS
Dominic ###-#### p/s o/h rec ok
ELE13-00060 Final12/18/201312/19/201312/19/2013 9:18:40 AMAPASS
Dennis Phone #: ###-#### PLEASE CALL BEFORE GOING OUT HVAC control final ok
ELE13-00060 Electrical Rough-In12/19/201312/19/201312/19/2013 9:18:01 AMPPASS
Dennis Phone #: ###-#### PLEASE CALL BEFORE GOING OUT HVAC control rough in ok
ELE13-02874 Permanent Service12/18/201312/19/201312/19/2013 8:38:28 AMAPASS
DON (SET FOR 8 AM PER ROCK) Phone #: ###-#### p/s o/h rec ok