ELE13-00368
| ELE-Aging Inspection | 12/19/2014 | 12/19/2014 | 12/24/2014 11:19:31 AM | | DONE |
|
|
Still under construction
|
ELE13-00373
| ELE-Aging Inspection | 12/19/2014 | 12/19/2014 | 12/19/2014 3:56:54 PM | | DONE |
|
|
Still under construction
|
ELE12-02580
| ELE-Aging Inspection | 12/19/2014 | 12/19/2014 | 12/19/2014 3:39:51 PM | | DONE |
|
|
Waiting on owner
|
ELE14-03221
| Final | 12/18/2014 | 12/19/2014 | 12/19/2014 2:46:11 PM | P | PASS |
|
|
8 solar panels on detached garage. AC micro-inverter system. No DC voltage. Enphase M250 Micro-Inverters, CSA, IEEE-1547, and UL-1741 listed. and 260 watt Suniva panels, ETL listed. A single home run, in conduit, is ran from solar array to the knife switch, located on the south corner of the detached garage in back yard. From the knife switch to the breaker in garage sub panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are clearly marked for solar, and the circuit number identified in the knife switch and the panel schedule. The inverters, panels and rails are all bonded with a number 6 ground that runs back to the sub panel electrode.
The sub panel that the solar array is landed to is in the garage, so give the homeowner a call for access at 208.375.7907
Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King Final ok
|
ELE14-03221
| Electrical Rough-In | 12/19/2014 | 12/19/2014 | 12/19/2014 2:08:05 PM | P | PASS |
|
|
8 solar panels on detached garage. AC micro-inverter system. No DC voltage. Enphase M250 Micro-Inverters, CSA, IEEE-1547, and UL-1741 listed. and 260 watt Suniva panels, ETL listed. A single home run, in conduit, is ran from solar array to the knife switch, located on the south corner of the detached garage in back yard. From the knife switch to the breaker in garage sub panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are clearly marked for solar, and the circuit number identified in the knife switch and the panel schedule. The inverters, panels and rails are all bonded with a number 6 ground that runs back to the sub panel electrode.
The sub panel that the solar array is landed to is in the garage, so give the homeowner a call for access at 208.375.7907
Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King Solar rough in ok
|
ELE14-03437
| Electrical Rough-In | 12/19/2014 | 12/19/2014 | 12/19/2014 2:05:07 PM | P | PASS |
|
|
Mike-wants ok on walls Phone #: ###-#### Wall rough in ok cover
|
ELE14-03489
| Electrical Rough-In | 12/19/2014 | 12/19/2014 | 12/19/2014 1:24:04 PM | P | PASS |
|
|
changing exterior lights to LEDs. LEDS are ETL and DLC listed Phone #: ###-#### Inspection requested via web by Tim Dunlop Verified listing of new fixtures. At time of inspection one complete on west side. Will call for final when complete
|
ELE14-03356
| Final | 12/19/2014 | 12/19/2014 | 12/19/2014 12:53:08 PM | P | PASS |
|
|
Owners are home. Thanks! Phone #: ###-#### Inspection requested via web by Lynn Solmon Final ok
|
ELE14-03464
| Rough-In Permanent Service | 12/19/2014 | 12/19/2014 | 12/19/2014 12:31:02 PM | P | FAIL |
|
|
Access man door back of garage Phone #: ###-#### Inspection requested via web by Lynn Solmon 210.52(B)- On print dining/den shall be wired with small appliance circuit for receptical outlets.
|
ELE14-02902
| Final | 12/18/2014 | 12/19/2014 | 12/19/2014 11:28:46 AM | A | FAIL |
|
|
Homeowner will be there. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan Patio cover installed after electrical. 680.26(B)- All fixed metal parts shall be bonded if located within 5' horizontal and 12' vertical of waters edge. Verbal with owner and contractor.
|
ELE14-01556
| Final | 12/18/2014 | 12/19/2014 | 12/19/2014 10:46:38 AM | A | PASS |
|
|
Swimming pool Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
|
ELE14-02928
| Final | 12/18/2014 | 12/19/2014 | 12/19/2014 9:39:30 AM | A | PASS |
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
|
ELE14-02930
| Final | 12/18/2014 | 12/19/2014 | 12/19/2014 9:35:48 AM | A | FAIL |
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas 210.8(A)(7)- Where receptical outlets are installed within 6' of edge of sink they shall have GFCI protection
|
ELE14-03272
| Final | 12/18/2014 | 12/19/2014 | 12/19/2014 8:32:41 AM | A | PASS |
|
|
Please call prior to inspection Phone #: ###-#### Inspection requested via web by BARRY KENDALL Final ok
|
ELE14-03455
| Rough-In Permanent Service | 12/19/2014 | 12/19/2014 | 12/19/2014 8:04:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|