Inspections for the day of: Friday, December 19, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00368 ELE-Aging Inspection12/19/201412/19/201412/24/2014 11:19:31 AM DONE
Still under construction
ELE13-00373 ELE-Aging Inspection12/19/201412/19/201412/19/2014 3:56:54 PM DONE
Still under construction
ELE12-02580 ELE-Aging Inspection12/19/201412/19/201412/19/2014 3:39:51 PM DONE
Waiting on owner
ELE14-03221 Final12/18/201412/19/201412/19/2014 2:46:11 PMPPASS
8 solar panels on detached garage.
AC micro-inverter system. No DC voltage.
Enphase M250 Micro-Inverters, CSA, IEEE-1547, and UL-1741 listed.
and 260 watt Suniva panels, ETL listed.
A single home run, in conduit, is ran from solar array to the knife switch, located on the south corner of the detached garage in back yard. From the knife switch to the breaker in garage sub panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are clearly marked for solar, and the circuit number identified in the knife switch and the panel schedule.
The inverters, panels and rails are all bonded with a number 6 ground that runs back to the sub panel electrode.

The sub panel that the solar array is landed to is in the garage, so give the homeowner a call for access at 208.375.7907

Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King Final ok
ELE14-03221 Electrical Rough-In12/19/201412/19/201412/19/2014 2:08:05 PMPPASS
8 solar panels on detached garage.
AC micro-inverter system. No DC voltage.
Enphase M250 Micro-Inverters, CSA, IEEE-1547, and UL-1741 listed.
and 260 watt Suniva panels, ETL listed.
A single home run, in conduit, is ran from solar array to the knife switch, located on the south corner of the detached garage in back yard. From the knife switch to the breaker in garage sub panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are clearly marked for solar, and the circuit number identified in the knife switch and the panel schedule.
The inverters, panels and rails are all bonded with a number 6 ground that runs back to the sub panel electrode.

The sub panel that the solar array is landed to is in the garage, so give the homeowner a call for access at 208.375.7907

Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King Solar rough in ok
ELE14-03437 Electrical Rough-In12/19/201412/19/201412/19/2014 2:05:07 PMPPASS
Mike-wants ok on walls Phone #: ###-#### Wall rough in ok cover
ELE14-03489 Electrical Rough-In12/19/201412/19/201412/19/2014 1:24:04 PMPPASS
changing exterior lights to LEDs. LEDS are ETL and DLC listed Phone #: ###-#### Inspection requested via web by Tim Dunlop Verified listing of new fixtures. At time of inspection one complete on west side. Will call for final when complete
ELE14-03356 Final12/19/201412/19/201412/19/2014 12:53:08 PMPPASS
Owners are home. Thanks! Phone #: ###-#### Inspection requested via web by Lynn Solmon Final ok
ELE14-03464 Rough-In Permanent Service12/19/201412/19/201412/19/2014 12:31:02 PMPFAIL
Access man door back of garage Phone #: ###-#### Inspection requested via web by Lynn Solmon 210.52(B)- On print dining/den shall be wired with small appliance circuit for receptical outlets.
ELE14-02902 Final12/18/201412/19/201412/19/2014 11:28:46 AMAFAIL
Homeowner will be there. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan Patio cover installed after electrical. 680.26(B)- All fixed metal parts shall be bonded if located within 5' horizontal and 12' vertical of waters edge. Verbal with owner and contractor.
ELE14-01556 Final12/18/201412/19/201412/19/2014 10:46:38 AMAPASS
Swimming pool Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
ELE14-02928 Final12/18/201412/19/201412/19/2014 9:39:30 AMAPASS
call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
ELE14-02930 Final12/18/201412/19/201412/19/2014 9:35:48 AMAFAIL
call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas 210.8(A)(7)- Where receptical outlets are installed within 6' of edge of sink they shall have GFCI protection
ELE14-03272 Final12/18/201412/19/201412/19/2014 8:32:41 AMAPASS
Please call prior to inspection Phone #: ###-#### Inspection requested via web by BARRY KENDALL Final ok
ELE14-03455 Rough-In Permanent Service12/19/201412/19/201412/19/2014 8:04:15 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok