Inspections for the day of: Friday, December 19, 2014.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-00904 FIRE-Final Inspection12/19/201412/19/201412/19/2014 3:50:25 PMPPART
Fire life safety inspection completed- Final pending project related fire sprinkler permit C/N items and final.
FIR14-00344 INSP-Sprinkler Rough-in12/18/201412/19/201412/19/2014 3:49:03 PMAPART
Inspection for 1st floor building C soffits completed- okayed for cover.
FIR14-00858 INSP-Sprinkler Rough-in12/19/201412/19/201412/19/2014 3:07:14 PMPPART
UG fire supply line tie-in verified and approved for bury.
FIR14-00849 INSP-Final Inspection12/18/201412/19/201412/19/2014 2:40:08 PMPPASS
Scope of fire alarm work completed and passed inspection. Permit finaled.
FIR14-00885 INSP-Sprinkler Rough-in12/19/201412/19/201412/19/2014 2:39:21 PMPPART
Overhead fire sprinkler modifications approved for cover.
FIR14-00830 INSP-Final Inspection12/18/201412/19/201412/19/2014 1:24:06 PMAPART
Completed link and MP tests. Final pending project related fire alarm permit work to supervise new hood system.
BLD14-02890 FIRE-Conference12/18/201412/19/201412/19/2014 1:21:47 PMADONE
On site conference regarding fire life safety inspection items and trade related alarm, sprinkler and hood suppression system work.
BLD14-02356 FIRE-Final Inspection12/18/201412/19/201412/19/2014 11:38:57 AMAPASS
Fire life safety inspection completed satisfactory. Signature card could not be located on site.
FIR14-00377 INSP-Final Inspection12/19/201412/19/201412/19/2014 11:37:14 AMPNR
Items needed prior to final include finish pack at the riser (signs, calc stickers, state tags), certify DCVA. Forward flow did not meet design specs.
FIR14-00832 INSP-Final Inspection12/18/201412/19/201412/19/2014 11:34:20 AMPPASS
Fire alarm inspection and testing passed. *Note- DSC replaced with AES via permit # FIR14-00877 prior to final. Permit finaled.
FIR14-00877 INSP-Final Inspection12/18/201412/19/201412/19/2014 11:28:24 AMAPASS
Fire alarm permit work passed field inspection and testing.
FIR13-00725 INSP-Sprinkler Rough-in12/18/201412/19/2014 P 
The inspection is on the 4th floor. Mike S is your contact. Please call 1/2 hour prior to inspection Phone #: ###-#### >> Inspection requested via web by Stan Beus