Inspections for the day of: Wednesday, December 19, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04737 Electrical Rough-In12/19/201812/19/201812/19/2018 3:14:21 PMPPASS
Damon Rush Phone #: ###-#### Inspection requested via web by Damon Rush
Raceway installations associated with elevator rough in ok cover.
ELE18-01330 Final12/18/201812/19/201812/19/2018 12:55:25 PMAFAIL
Please call 30min in advance so I can meet on site with you. Phone #: ###-#### Inspection requested via web by Casey Fouts
210.8- GFCI protection shall be provided for all 120 volt receptacle outlets up to 50 amp and other than 120 volt receptacles up to 100 amp.
300.11- Luminaires located in kitchen areas shall be supported independant of grid
300.15- Bath fan hanging from ceiling with splice not contained in a box. All aplices shall be contained in a box or enclosure.
422.31- A disconnecting means shall be provided for a appliances rated over 300 VA that shall be located with in 50' and with in sight of appliance.
* All electrical power associated with hood shall be connected to ansil system to disconnect power in case of fire.
ELE18-03175 Final12/19/201812/19/201812/19/2018 11:51:15 AMAPASS
The home owners and workers will be there to let you in. Phone #: ###-#### Inspection requested via web by Jay Symonds
Final ok
ELE18-04737 Final12/18/201812/19/201812/19/2018 11:20:25 AMANH
Inspect portion Phone #: ###-#### Inspection requested via web by Damon Rush No answer, recall when available
ELE18-03802 Electrical Rough-In12/18/201812/19/201812/19/2018 10:53:15 AMAPASS
Randy. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Grid complete rough in ok cover
ELE18-03890 Electrical Rough-In12/17/201812/19/201812/19/2018 10:52:31 AMAPASS
A ceiling grid inspection is needed. Please call Lynn at ###-#### prior to arrival so that he can meet the inspector in the elevator. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor
Offices grid rough in ok cover
ELE18-04413 Final12/18/201812/19/201812/19/2018 9:53:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
110.24- Available fault current shall be posted with value and date calculated.
210.63- A service receptacle outlet shall be installed with in 25' of outdoor AC unit and on mezz with in 25' of air handler.
314.25- Open j-box north wall warehouse for exhaust fan.
330.30- MC located on mezz shall be secured to wall.
406.6- GFCI receptacle located in warehouse bathroom shall have a cover.
IBC- Power for emergency light shall not be controlled by a wall switch.