ELE18-04637
| Electrical Rough-In | 12/19/2018 | 12/19/2018 | 12/19/2018 4:13:45 PM | P | PASS |
|
|
R/I inspection spinning room area 2. Call Bobby, thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo Spinning room ceiling only ok to cover
|
ELE18-04719
| Temporary Service | 12/19/2018 | 12/19/2018 | 12/19/2018 12:47:09 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE18-04771
| Electrical Rough-In | 12/18/2018 | 12/19/2018 | 12/19/2018 12:13:54 PM | A | PASS |
|
|
For access please call Jaman 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott main bath and up master bath rough in ok
|
ELE11-01976
| Final | 12/18/2018 | 12/19/2018 | 12/19/2018 11:33:42 AM | A | PASS |
|
|
For access please call Jaman 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott Final ok
|
ELE18-03635
| Final | 12/14/2018 | 12/19/2018 | 12/19/2018 11:27:24 AM | A | FAIL |
|
|
There will be someone home. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan AFCI breaker installed instead of GFCI for garage feed. Missing KO seal in bottom of panel. Mislabeled panel schedule. Slip joint installed upside down.
|
ELE18-03420
| Final | 12/18/2018 | 12/19/2018 | 12/19/2018 10:35:55 AM | A | PASS |
|
|
garage code 1624 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE18-03526
| Final | 12/18/2018 | 12/19/2018 | 12/19/2018 10:35:32 AM | A | PASS |
|
|
garage code 1824 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE18-03538
| Final | 12/18/2018 | 12/19/2018 | 12/19/2018 10:35:05 AM | A | FAIL |
|
|
garage code 1724 Phone #: ###-#### Inspection requested via web by Darryn Coburn Max overcurrent on A/C nameplate is 20A(30A installed) Missing panel cover screws. Garage receps showing Hot/Ground reverse while GFCI recep tripped.
|
ELE18-04734
| Rough-In Permanent Service | 12/18/2018 | 12/19/2018 | 12/19/2018 9:50:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|
ELE18-04637
| Electrical Rough-In | 12/19/2018 | 12/19/2018 | 12/19/2018 9:30:50 AM | A | PART |
|
|
Please call Bobby for inspection of ceiling in area C 1st floor and grid ceiling on 2nd floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo 2nd floor area C minus Spinning room 202. 1st floor restrooms area C Ceilings only ok to cover
|