FIR02-00371 INSP-Final Inspection11/27/200212/2/200212/2/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 11/27/2002 at 14:09:46. Contact: ###-####. this permit has been superceded by permit FIR02-00441 12/2/2002 8:36:49 AM
BLD02-02708 FIRE-Final Inspection11/27/200212/2/200212/2/2002 12:00:00 AMAFAIL
###-#### need fire alarm testing completed for FIR00-00702 prior to occ 12/2/2002 1:30:12 PM
MIS02-00311 FIR-Final12/2/200212/2/200212/2/2002 12:00:00 AMPFAIL
###-#### EARLY PM CALL FIRST need extinguisher and "Door to remain unlocked during business hours" sign at mmain exit 12/2/2002 1:18:39 PM
BLD02-00175 FIRE-Final Inspection12/2/200212/2/200212/2/2002 12:00:00 AMPFAIL
###-#### supervised ball valves needed for antifreeze system; temporal horns in rooms; record of completion 12/2/2002 4:47:48 PM
FIR02-00399 INSP-Final Inspection12/2/200212/2/200212/2/2002 12:00:00 AMPCANC
###-#### rescheduled for 12/4 12/3/2002 10:50:46 AM
FIR02-00318 INSP-Final Inspection12/2/200212/2/200212/2/2002 12:00:00 AMPFAIL
tampers at anti-freeze system not supervised
FIR02-00402 INSP-Alarm Testing11/27/200212/2/200212/2/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 11/27/2002 at 13:47:12. Contact: ###-####. need temporal tone in rooms; record of completion; supervised ball valves for tampers at anti-freeze system 12/2/2002 4:46:58 PM