BLD02-02490
| FIRE-Final Inspection | 11/29/2002 | 12/2/2002 | 12/2/2002 12:00:00 AM | A | PASS |
|
|
fire life/safety finaled 12/2/2002 9:56:27 AM
|
BLD02-01331
| BLD-Other | 12/2/2002 | 12/2/2002 | 12/2/2002 12:00:00 AM | A | DONE |
|
|
I stopped by the project to verify wether the sprinkler system had been left in service per code requirement. I found a large pile of sprinkler piping including pendant drops, sprinkler mains, earth quaking and hangers in a pile just outside of the main entrance. I was unable to access the interior of the building but could look through the lobby glass. From what I could see there appears to be no sprinkler protection in the lobby area and it also appears that there is part of the open sprinkler system still hanging from the structure just inside of the lobby area
|
FIR02-00332
| INSP-Alarm Testing | 11/26/2002 | 12/2/2002 | 12/2/2002 12:00:00 AM | P | CANC |
|
|
cancelled by the contractor until tomorrow 12/2/2002 4:25:30 PM
|
BLD02-01720
| FIRE-Final Inspection | 12/2/2002 | 12/2/2002 | 12/2/2002 12:00:00 AM | P | FAIL |
|
|
smoke exhaust system does not operate correctly. The louver appears to be stuck 12/2/2002 4:27:37 PM
|