Inspections for the day of: Monday, December 2, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02490 FIRE-Final Inspection11/29/200212/2/200212/2/2002 12:00:00 AMAPASS
fire life/safety finaled 12/2/2002 9:56:27 AM
BLD02-01331 BLD-Other12/2/200212/2/200212/2/2002 12:00:00 AMADONE
I stopped by the project to verify wether the sprinkler system had been left in service per code requirement. I found a large pile of sprinkler piping including pendant drops, sprinkler mains, earth quaking and hangers in a pile just outside of the main entrance. I was unable to access the interior of the building but could look through the lobby glass. From what I could see there appears to be no sprinkler protection in the lobby area and it also appears that there is part of the open sprinkler system still hanging from the structure just inside of the lobby area
FIR02-00332 INSP-Alarm Testing11/26/200212/2/200212/2/2002 12:00:00 AMPCANC
cancelled by the contractor until tomorrow 12/2/2002 4:25:30 PM
BLD02-01720 FIRE-Final Inspection12/2/200212/2/200212/2/2002 12:00:00 AMPFAIL
smoke exhaust system does not operate correctly. The louver appears to be stuck 12/2/2002 4:27:37 PM