Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00563 INSP-Sprinkler Rough-in/Hydro12/2/200312/2/200312/2/2003 12:00:00 AMAFAIL
two heads of of 1" outlet in address 8170, 8172 and 8176. No pendant in restroom and upright overspaced near restroom in address 8174. Upright overspaced along east wall in address 8184. Plans show 1 1/4" branchlines and 2" far main. 1 1/2" branchlines and 3" far main is installed. Calcs show Dyna Flow pipe but Sch. 40 is installed. Resubmit plans with everything corrected. No other items inspected. Underground flush failed. Hydro test failed on the overhead system. Hydro test passed on canopy system