Inspections for the day of: Thursday, December 2, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03737 Final11/30/200412/2/200412/2/2004 12:00:00 AMAPASS
Chris; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final, told owner to finish panel sched. 12/2/2004 9:02:12 AM
ELE04-03568 Electrical Rough-In12/1/200412/2/200412/2/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/1/2004 at 12:37:28 PM. Contact: ###-####. rough-in cover ok p/s u/g n ok 12/2/2004 9:55:27 AM
ELE04-02595 Conference12/1/200412/2/200412/2/2004 12:00:00 AMADONE
Scheduled by a contractor via Hello! on 12/1/2004 at 1:07:36 PM. Contact: ###-####. Electrical room is too small, they asked if we could reduce clearance and I said no. They can easily move wall. Required for 3 rooms only. 2,3,4, floor. 12/2/2004 10:27:55 AM
ELE04-03740 Electrical Rough-In12/1/200412/2/200412/2/2004 12:00:00 AMAPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, ok to cover. p/s u/g n ok 12/2/2004 8:26:45 AM
ELE04-03705 Rough-In Permanent Service12/1/200412/2/200412/2/2004 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn cover oki p/s u/g n ok . called contractor about recpt spacing at fireplace. 12/2/2004 11:00:09 AM
ELE04-03734 Permanent Service12/2/200412/2/200412/2/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/2/2004 at 7:28:15 AM. Contact: ###-####. water pipe bond done. ok to final. 12/2/2004 9:27:57 AM
ELE04-03770 Temporary Service12/2/200412/2/200412/2/2004 12:00:00 AMPFAIL
danette ###-#### 250.30(A)(4) shall supply grounding electrode, BCC Shall affix job id sticker. 12/2/2004 3:12:28 PM
ELE04-03223 Final12/2/200412/2/200412/2/2004 12:00:00 AMPPASS
don - Note: permanent service; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final p/s u/g n ok 12/2/2004 1:56:20 PM
ELE04-03760 Electrical Rough-In12/2/200412/2/200412/2/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/2/2004 at 10:27:34 AM. Contact: ###-####. called contr. to add gnd. screws, and strap mc cable. ok to cover wall. 12/2/2004 1:26:39 PM
ELE04-02862 Permanent Service12/2/200412/2/200412/2/2004 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 12/2/2004 at 10:29:42 AM. Contact: ###-####. no ufer access, ground wire to be landed and stripped of insulation. Call when ready. 12/2/2004 4:28:32 PM
ELE04-03724 Final11/29/200412/2/200412/2/2004 12:00:00 AMPPASS
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok for power, p/s u/g exst. ok 12/2/2004 12:40:19 PM