Inspections for the day of: Thursday, December 2, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01022 FIRE-Final Inspection12/1/200412/2/200412/2/2004 6:39:23 AMACANC
Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry
BLD04-00349 FIRE-Final Inspection12/1/200412/2/200412/2/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/1/2004 at 1:35:36 PM. Contact: ###-####. Will have address up for structural inspector 12/2/2004 8:45:03 AM
BLD04-00217 FIRE-Final Inspection12/1/200412/2/200412/2/2004 12:00:00 AMAFAIL
kent; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Address posted - the GC said the address has changed to Front St. - told him to correct this with PDS; extinguishers needed; bollards needed at gas meter on north side 12/2/2004 11:34:10 AM
FIR04-00721 INSP-Final Inspection12/1/200412/2/200412/2/2004 12:00:00 AMPFAIL
If possible schedule final inspection for FIR04-00709 at the same time. Request 3:00 PM inspection.; Phone #: ###-#### Internet Inspection Request from: Michael Heath Could not test as the lights weren't operational to verify shunt of lights; alarm signal to panel okay 12/2/2004 4:02:49 PM
FIR04-00652 INSP-Final Inspection12/2/200412/2/200412/2/2004 12:00:00 AMPPASS
FIR04-00709 INSP-Final Inspection12/2/200412/2/200412/2/2004 12:00:00 AMPFAIL
Supervisory signals latch; update map to show all initiating devices 12/2/2004 4:15:00 PM
BLD04-02240 FIRE-Final Inspection12/2/200412/2/200412/2/2004 12:00:00 AMPFAIL
Complete fire alarm and hood permits; address visible from street; sprinkler needs annual certification; sign above main door ....when occupied"; keys in knox box 12/2/2004 4:08:54 PM