Inspections for the day of: Friday, December 2, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03647 Final12/1/200512/2/200512/6/2005 9:33:01 AMAFAIL
bob moore jr.; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
called corrections not made
ELE05-04154 Electrical Rough-In12/2/200512/2/200512/2/2005 4:18:16 PMPPASS
for carport cover- delbert ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ELE05-04337 Electrical Rough-In12/2/200512/2/200512/2/2005 3:39:24 PMPPASS
darrell ###-#### u/g and garage ok
ELE05-04336 Electrical Rough-In12/2/200512/2/200512/2/2005 3:22:05 PMPPASS
DARELL ###-#### u/g and garage ok
ELE05-04278 Electrical Rough-In12/2/200512/2/200512/2/2005 2:26:38 PMPFAIL
Scheduled by a contractor via Hello! on 12/2/2005 at 11:13:35 AM. Contact: ###-####. r/i for u/g ok only, called needs to update permit for p/s and 1 rm, needs shed to meet part II of art 225, 250.32, 210.70
ELE05-04277 Electrical Rough-In12/2/200512/2/200512/2/2005 2:24:19 PMPFAIL
Scheduled by a contractor via Hello! on 12/2/2005 at 11:12:23 AM. Contact: ###-####. not ready called 300.4 11/4" 314.3 110.3(B) needs bond bushing or non metallic conn. at spa disconnect, also needs to update permit for spa and 1 rm
ELE05-03286 Final12/2/200512/2/200512/2/2005 1:34:44 PMPFAIL
Large overhead door will push open for access.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas new cor. notice posted created more violations, fee due also called left message, 314.16 box fill, island counter, 314.17 replace cutin boxes with broken cable clamps
ELE05-03422 Final12/2/200512/2/200512/2/2005 1:10:48 PMPFAIL
Scheduled by a contractor via Hello! on 12/2/2005 at 10:50:28 AM. Contact: ###-####. new cor. posted also fee due,called 314.43 remove madison clamp from plastic box, for refer under dinning rm counter 356.42 shall use listed conn. for LNFC, outlet end of peninsular counter
ELE05-04330 Permanent Service12/1/200512/2/200512/2/2005 12:42:33 PMAPART
lynn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok only cor. posted for r/i and final 210.70 switch and fixtures required for outside exit doors, 300.4 and 334.15 needs 11/4", and run exposed cables so protected as code noted states 312. 5 conn for GEC
ELE05-04329 Permanent Service12/1/200512/2/200512/2/2005 12:38:59 PMAPART
lynn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok only cor. for r/i and final, 250.52,104(A)(1) grd or bond to water system,110.3(B) and B C C use manufactures listed breakers, breaker tie bars, remove old GEC , label circuits, all cables need connectors ( subpanel) 312.5 conn. for GEC, 240.24 6ft 7" for breaker at p/s
ELE05-03459 Final12/1/200512/2/200512/2/2005 9:05:58 AMAFAIL
Garage code - 2010.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor fee due posted called left message 213.22 flex not long enough to allow required access to box, 314.16 b0x fill MB bath also 250.148 grd boxes 210.52(A) outlet spacing MB N wall, is outside paddle fan listed for wet location ? need proof
ELE05-03730 Electrical Rough-In12/2/200512/2/200512/2/2005 12:00:00 AMPFAIL
cor. posted uncover all u/g conduit covered before inspection
ELE05-04336 Final12/2/200512/2/200512/2/2005 12:00:00 AMPPASS
DARELL ###-#### ok
ELE05-04337 Final12/2/200512/2/200512/2/2005 12:00:00 AMPPASS
darrell ###-####ok
ELE02-02940 Permanent Service12/1/200512/2/200512/1/2005 5:05:14 PMAPART
dave --re-insp -call 1st before insp homeowner; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added p/s for 12-01-05 owner will finish work and call for final when done either 12-02-05 or 12-05-05 am
ELE02-02940 Permanent Service12/1/200512/2/200512/1/2005 1:42:22 PMAFAIL
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
cor. posted met with owner, 312.5 needs conn. for GEC, 250.148, ged jbox attic, splice all equip grds together, and tag box with #10 copper,110.14 use approved copper - aulm devices to splice cu/al, 250.52(A)(1), shall grd water system at p/s #4 copper, 110.3(B) shall use manufactures means to bond sub panel note not bonded with any means now, 314.17(D) bushings for #4 and larger,250.90&92 shall bond conduit bottom of meterbase #4 copper