Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00450 INSP-Sprinkler Rough-in11/27/201312/2/201312/18/2013 4:57:54 PMPPART
FIR13-00628 INSP-Sprinkler Rough-in12/2/201312/2/201312/3/2013 7:42:40 AMPDEFR
To 12/3
FIR13-00233 INSP-Alarm Testing12/2/201312/2/201312/3/2013 7:40:03 AMPPART
Please call prior to inspection or ###-#### Johnathon Phone #: ###-#### *For low air monitor modules a three dry systems*
FIR12-00721 INSP-Final Inspection11/27/201312/2/201312/3/2013 7:37:50 AMAPART
Need to relocate outside bell at the main street side above the correct FDC, 1st floor tenant work underway.
FIR13-00011 INSP-Final Inspection11/27/201312/2/201312/3/2013 7:31:52 AMAPART
Completed trip testing for new dry systems at the 3rd, 4th, and 5th floor parking garage levels. Also noted obstructed upright coverage at the service elevator lobbies typical most floors 6-15, missing hangers on mains parallel to and beneath stairways, temporary construction office at the NE corner of the 10th floor disrupts shell coverage. Final shell walkthrough incomplete at this time.
FIR13-00133 INSP-Final Inspection11/27/201312/2/201312/3/2013 7:22:36 AMAPART
Noted a large non-sprinklered area above the 17th floor SE corner, remove foil at upright heads in the penthouse, provide access to the electrical room penthouse level for inspection, need signage at the control valve for the roof top hose connection, upright at the 16th floor service elevator lobby is blocked. 17th floor TI work underway.
FIR12-00605 INSP-Final Inspection11/27/201312/2/201312/3/2013 7:13:20 AMAPASS
UG fire supply line permit finaled.
FIR12-00634 INSP-Final Inspection11/27/201312/2/201312/3/2013 7:05:18 AMAPART
Missing valve caps at several locations.
FIR12-00681 INSP-Final Inspection11/27/201312/2/201312/3/2013 7:04:03 AMAPART
Need to remove valves in the pressure sensing lines per NFPA 20, pump room still missing ventilation, floor drain does not function, final walkthrough at the basement incomplete.
FIR13-00440 INSP-Sprinkler Rough-in/Hydro12/2/201312/2/201312/2/2013 8:35:21 PMPPART
Completed hydrostatic test of the new suction piping at the fire pump.
BLD13-02638 FIRE-Final Inspection11/30/201312/2/201312/2/2013 1:29:50 PMAPASS
Fire life safety inspection passed.