FIR13-00450
| INSP-Sprinkler Rough-in | 11/27/2013 | 12/2/2013 | 12/18/2013 4:57:54 PM | P | PART |
|
|
|
FIR13-00628
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/2/2013 | 12/3/2013 7:42:40 AM | P | DEFR |
|
|
To 12/3
|
FIR13-00233
| INSP-Alarm Testing | 12/2/2013 | 12/2/2013 | 12/3/2013 7:40:03 AM | P | PART |
|
|
Please call prior to inspection or ###-#### Johnathon Phone #: ###-#### *For low air monitor modules a three dry systems*
|
FIR12-00721
| INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 7:37:50 AM | A | PART |
|
|
Need to relocate outside bell at the main street side above the correct FDC, 1st floor tenant work underway.
|
FIR13-00011
| INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 7:31:52 AM | A | PART |
|
|
Completed trip testing for new dry systems at the 3rd, 4th, and 5th floor parking garage levels. Also noted obstructed upright coverage at the service elevator lobbies typical most floors 6-15, missing hangers on mains parallel to and beneath stairways, temporary construction office at the NE corner of the 10th floor disrupts shell coverage. Final shell walkthrough incomplete at this time.
|
FIR13-00133
| INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 7:22:36 AM | A | PART |
|
|
Noted a large non-sprinklered area above the 17th floor SE corner, remove foil at upright heads in the penthouse, provide access to the electrical room penthouse level for inspection, need signage at the control valve for the roof top hose connection, upright at the 16th floor service elevator lobby is blocked. 17th floor TI work underway.
|
FIR12-00605
| INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 7:13:20 AM | A | PASS |
|
|
UG fire supply line permit finaled.
|
FIR12-00634
| INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 7:05:18 AM | A | PART |
|
|
Missing valve caps at several locations.
|
FIR12-00681
| INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 7:04:03 AM | A | PART |
|
|
Need to remove valves in the pressure sensing lines per NFPA 20, pump room still missing ventilation, floor drain does not function, final walkthrough at the basement incomplete.
|
FIR13-00440
| INSP-Sprinkler Rough-in/Hydro | 12/2/2013 | 12/2/2013 | 12/2/2013 8:35:21 PM | P | PART |
|
|
Completed hydrostatic test of the new suction piping at the fire pump.
|
BLD13-02638
| FIRE-Final Inspection | 11/30/2013 | 12/2/2013 | 12/2/2013 1:29:50 PM | A | PASS |
|
|
Fire life safety inspection passed.
|