Inspections for the day of: Tuesday, December 2, 2014.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03283 Final12/2/201412/2/201412/2/2014 3:53:10 PMPPASS
Eric Phone #: ###-####
Final OK
ELE14-03283 Permanent Service12/2/201412/2/201412/2/2014 3:46:33 PMPPASS
Eric Phone #: ###-####
PS, OH, RC, OK
ELE14-03314 Permanent Service12/2/201412/2/201412/2/2014 3:05:16 PMPFAIL
Sam Phone #: ###-####
BCC4.05.15 Work must be performed by licensed electrical contractor
250.68(A) Ground shall be accessible , no meter connection
250.53(d)2 Supplemental ground required
110.26 working space required at meter
408.41 Each grounded conductor shall terminate individually on bar
210.5(c) ungrounded conductors shall be identified
210.4(b) multiwired branch circuits shall disconnect simultaneously_ Handle ties
408.36(d) backfed device requires additional fastener
110.12A unused openings shall be closedd for protectioin, meter base and subpanel
ELE14-02229 Electrical Rough-In12/2/201412/2/201412/2/2014 1:04:47 PMPPASS
Dan Phone #: ###-####
Grounds connected, check for ground to all switches for final..
ELE14-03006 Final12/2/201412/2/201412/2/2014 12:44:16 PMPCANC
Inspect conduit in front step concrete forms. Phone #: ###-#### Inspection requested via web by Terry Scott
Needed RI
ELE14-03299 Electrical Rough-In12/2/201412/2/201412/2/2014 12:42:24 PMPNH
contact - Joe Levitch ###-#### Phone #: ###-#### Inspection requested via web by Andy Derrick
left message, no access, left notice on door
ELE14-02983 Final12/2/201412/2/201412/2/2014 12:41:34 PMPPASS
David Phone #: ###-####
Final OK
ELE14-03006 Electrical Rough-In12/2/201412/2/201412/2/2014 12:18:51 PMPPASS
Inspect conduit in front step concrete forms. Phone #: ###-#### Inspection requested via web by Terry Scott

Conduit in front concrete steps, ok to cover
ELE14-03295 Temporary Service12/2/201412/2/201412/2/2014 12:01:00 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
TS, UG, N, OK
ELE14-03296 Rough-In Permanent Service12/2/201412/2/201412/2/2014 12:00:17 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
Corrections made, RI OK
PS, UG, N, OK
ELE11-02581 ELE-Aging Inspection12/2/201412/2/201412/2/2014 11:06:21 AM DONE
Left correction notice on door and spoke with electrical contractor
ELE14-03117 Rough-In Permanent Service12/2/201412/2/201412/2/2014 10:36:48 AMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
RI OK, PS, UG, N, OK
ELE12-00989 ELE-Aging Inspection12/2/201412/2/201412/2/2014 9:54:15 AM DONE
Posted correction notice on front door and left contractor a message
ELE14-03014 Final12/1/201412/2/201412/2/2014 9:26:50 AMAPASS
Frank @ ###-#### Phone #: ###-#### Inspection requested via web by Kristopher Wilson
FInal OK
ELE14-02233 Final12/1/201412/2/201412/2/2014 9:07:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Burke

See permit ELE14-01556 for pool equipment
FInal OK
ELE14-02229 Electrical Rough-In12/1/201412/2/201412/2/2014 8:36:26 AMACANC
call 10min before//dan Phone #: ###-####
Turned into conference
ELE14-02229 Conference12/2/201412/2/201412/2/2014 8:36:00 AMPDONE
call 10min before//dan Phone #: ###-####
Needs to have grounding made up in all boxes for visual inspection prior to cover, need GFI protection on receptacles being used in garage