ELE14-03283
| Final | 12/2/2014 | 12/2/2014 | 12/2/2014 3:53:10 PM | P | PASS |
|
|
Eric Phone #: ###-#### Final OK
|
ELE14-03283
| Permanent Service | 12/2/2014 | 12/2/2014 | 12/2/2014 3:46:33 PM | P | PASS |
|
|
Eric Phone #: ###-#### PS, OH, RC, OK
|
ELE14-03314
| Permanent Service | 12/2/2014 | 12/2/2014 | 12/2/2014 3:05:16 PM | P | FAIL |
|
|
Sam Phone #: ###-#### BCC4.05.15 Work must be performed by licensed electrical contractor 250.68(A) Ground shall be accessible , no meter connection 250.53(d)2 Supplemental ground required 110.26 working space required at meter 408.41 Each grounded conductor shall terminate individually on bar 210.5(c) ungrounded conductors shall be identified 210.4(b) multiwired branch circuits shall disconnect simultaneously_ Handle ties 408.36(d) backfed device requires additional fastener 110.12A unused openings shall be closedd for protectioin, meter base and subpanel
|
ELE14-02229
| Electrical Rough-In | 12/2/2014 | 12/2/2014 | 12/2/2014 1:04:47 PM | P | PASS |
|
|
Dan Phone #: ###-#### Grounds connected, check for ground to all switches for final..
|
ELE14-03006
| Final | 12/2/2014 | 12/2/2014 | 12/2/2014 12:44:16 PM | P | CANC |
|
|
Inspect conduit in front step concrete forms. Phone #: ###-#### Inspection requested via web by Terry Scott Needed RI
|
ELE14-03299
| Electrical Rough-In | 12/2/2014 | 12/2/2014 | 12/2/2014 12:42:24 PM | P | NH |
|
|
contact - Joe Levitch ###-#### Phone #: ###-#### Inspection requested via web by Andy Derrick left message, no access, left notice on door
|
ELE14-02983
| Final | 12/2/2014 | 12/2/2014 | 12/2/2014 12:41:34 PM | P | PASS |
|
|
David Phone #: ###-#### Final OK
|
ELE14-03006
| Electrical Rough-In | 12/2/2014 | 12/2/2014 | 12/2/2014 12:18:51 PM | P | PASS |
|
|
Inspect conduit in front step concrete forms. Phone #: ###-#### Inspection requested via web by Terry Scott
Conduit in front concrete steps, ok to cover
|
ELE14-03295
| Temporary Service | 12/2/2014 | 12/2/2014 | 12/2/2014 12:01:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov TS, UG, N, OK
|
ELE14-03296
| Rough-In Permanent Service | 12/2/2014 | 12/2/2014 | 12/2/2014 12:00:17 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Corrections made, RI OK PS, UG, N, OK
|
ELE11-02581
| ELE-Aging Inspection | 12/2/2014 | 12/2/2014 | 12/2/2014 11:06:21 AM | | DONE |
|
|
Left correction notice on door and spoke with electrical contractor
|
ELE14-03117
| Rough-In Permanent Service | 12/2/2014 | 12/2/2014 | 12/2/2014 10:36:48 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn RI OK, PS, UG, N, OK
|
ELE12-00989
| ELE-Aging Inspection | 12/2/2014 | 12/2/2014 | 12/2/2014 9:54:15 AM | | DONE |
|
|
Posted correction notice on front door and left contractor a message
|
ELE14-03014
| Final | 12/1/2014 | 12/2/2014 | 12/2/2014 9:26:50 AM | A | PASS |
|
|
Frank @ ###-#### Phone #: ###-#### Inspection requested via web by Kristopher Wilson FInal OK
|
ELE14-02233
| Final | 12/1/2014 | 12/2/2014 | 12/2/2014 9:07:53 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Burke
See permit ELE14-01556 for pool equipment FInal OK
|
ELE14-02229
| Electrical Rough-In | 12/1/2014 | 12/2/2014 | 12/2/2014 8:36:26 AM | A | CANC |
|
|
call 10min before//dan Phone #: ###-#### Turned into conference
|
ELE14-02229
| Conference | 12/2/2014 | 12/2/2014 | 12/2/2014 8:36:00 AM | P | DONE |
|
|
call 10min before//dan Phone #: ###-#### Needs to have grounding made up in all boxes for visual inspection prior to cover, need GFI protection on receptacles being used in garage
|