ELE15-03790
| Electrical Rough-In | 12/1/2015 | 12/2/2015 | 12/2/2015 2:20:33 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Matthew White Northwest corner of intersection of porsche and avanti pole base in common area. Underground and pole base rough in ok cover
|
ELE15-02922
| Final | 12/1/2015 | 12/2/2015 | 12/2/2015 1:59:38 PM | P | PASS |
|
|
Damon Barr will be the electrician on site ###-#### Phone #: ###-#### Inspection requested via web by Liz Ramsey Closet luminaires chenged to florescent. Final ok
|
ELE15-03808
| Electrical Rough-In | 12/2/2015 | 12/2/2015 | 12/2/2015 1:32:44 PM | P | PASS |
|
|
We are requesting a rough-in inspection on the soffit for today in the afternoon. Our contact for this project is Trent ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Interior soffits rough in ok cover
|
ELE15-03732
| Rough-In Permanent Service | 12/2/2015 | 12/2/2015 | 12/2/2015 1:09:10 PM | P | PASS |
|
|
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|
ELE15-03851
| Temporary Service | 12/1/2015 | 12/2/2015 | 12/2/2015 11:45:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
|
ELE15-03865
| Temporary Service | 12/1/2015 | 12/2/2015 | 12/2/2015 11:34:19 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson No temp pole set on this lot. Called contact number no answer mailbox is full unable to leave message.
|
ELE15-03864
| Temporary Service | 12/1/2015 | 12/2/2015 | 12/2/2015 11:30:31 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|
MIS15-00297
| ELE-Conference | 12/2/2015 | 12/2/2015 | 12/2/2015 11:16:23 AM | A | DONE |
|
|
Discussed with owner who added light fixtures to space that flexible cord shall not be used for permenant wiring or installed above ceiling grid as per NEC 400.8. Also discussed open spices. All cords and cables shall terminate in a box as per NEC 300.15 As I documented findings owner removed all cords that were in violation.
|
MIS15-00297
| ELE-Final | 12/2/2015 | 12/2/2015 | 12/2/2015 11:16:04 AM | P | FAIL |
|
|
Owner removed flexible cords as notes were being made. Final ok
|
ELE15-03167
| Temporary Service | 12/1/2015 | 12/2/2015 | 12/2/2015 10:23:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE15-03867
| Electrical Rough-In | 12/1/2015 | 12/2/2015 | 12/2/2015 9:53:21 AM | A | PASS |
|
|
Please call for access code Phone #: ###-#### Inspection requested via web by Rick Beckman Grid and wall rough in ok cover
|
ELE15-02478
| Final | 12/1/2015 | 12/2/2015 | 12/2/2015 9:30:04 AM | A | FAIL |
|
|
Garage Code 5248. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.52(C)(4)- If area behind sink is 12" or greater deep sink does not seperate counter space. Receptacle outlet required behind sink. 330.30(B)- MC ran to peninsula box shall be secured with in 12" of box. 408.4- Circuit directory shall accurately identify branch circuits and main. Lock box code is 1976
|
ELE15-03290
| Final | 12/1/2015 | 12/2/2015 | 12/2/2015 8:48:26 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
ELE15-03732
| Rough-In Permanent Service | 12/2/2015 | 12/2/2015 | 12/2/2015 7:40:24 AM | A | CANC |
|
|
Please contact Gary ###-#### with any questions Phone #: ###-#### >> Inspection requested via web by Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|