Inspections for the day of: Wednesday, December 2, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03790 Electrical Rough-In12/1/201512/2/201512/2/2015 2:20:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Matthew White
Northwest corner of intersection of porsche and avanti pole base in common area. Underground and pole base rough in ok cover
ELE15-02922 Final12/1/201512/2/201512/2/2015 1:59:38 PMPPASS
Damon Barr will be the electrician on site ###-#### Phone #: ###-#### Inspection requested via web by Liz Ramsey Closet luminaires chenged to florescent. Final ok
ELE15-03808 Electrical Rough-In12/2/201512/2/201512/2/2015 1:32:44 PMPPASS
We are requesting a rough-in inspection on the soffit for today in the afternoon. Our contact for this project is Trent ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Interior soffits rough in ok cover
ELE15-03732 Rough-In Permanent Service12/2/201512/2/201512/2/2015 1:09:10 PMPPASS
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-03851 Temporary Service12/1/201512/2/201512/2/2015 11:45:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
t/s u/g n ok
ELE15-03865 Temporary Service12/1/201512/2/201512/2/2015 11:34:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by David Nelson No temp pole set on this lot. Called contact number no answer mailbox is full unable to leave message.
ELE15-03864 Temporary Service12/1/201512/2/201512/2/2015 11:30:31 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
MIS15-00297 ELE-Conference12/2/201512/2/201512/2/2015 11:16:23 AMADONE
Discussed with owner who added light fixtures to space that flexible cord shall not be used for permenant wiring or installed above ceiling grid as per NEC 400.8.
Also discussed open spices. All cords and cables shall terminate in a box as per NEC 300.15
As I documented findings owner removed all cords that were in violation.
MIS15-00297 ELE-Final12/2/201512/2/201512/2/2015 11:16:04 AMPFAIL
Owner removed flexible cords as notes were being made. Final ok
ELE15-03167 Temporary Service12/1/201512/2/201512/2/2015 10:23:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-03867 Electrical Rough-In12/1/201512/2/201512/2/2015 9:53:21 AMAPASS
Please call for access code Phone #: ###-#### Inspection requested via web by Rick Beckman Grid and wall rough in ok cover
ELE15-02478 Final12/1/201512/2/201512/2/2015 9:30:04 AMAFAIL
Garage Code 5248. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
210.52(C)(4)- If area behind sink is 12" or greater deep sink does not seperate counter space. Receptacle outlet required behind sink.
330.30(B)- MC ran to peninsula box shall be secured with in 12" of box.
408.4- Circuit directory shall accurately identify branch circuits and main.
Lock box code is 1976
ELE15-03290 Final12/1/201512/2/201512/2/2015 8:48:26 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
Final ok
ELE15-03732 Rough-In Permanent Service12/2/201512/2/201512/2/2015 7:40:24 AMACANC
Please contact Gary ###-#### with any questions Phone #: ###-#### >> Inspection requested via web by Tracy Robertson Inspection cancelled from web by: Tracy Robertson