FIR15-00821
| INSP-Sprinkler Rough-in/Hydro | 12/2/2015 | 12/2/2015 | 12/2/2015 3:28:06 PM | P | PART |
|
|
Rough-in installation looks good except the new pendants that have been added in the soffit that was not shown on the plans need to meet NFPA 13-8.6.4.1.1.3. Plans/hydraulic calculations will need to be verified by plan review.
|
FIR15-00842
| INSP-Final Inspection | 12/2/2015 | 12/2/2015 | 12/2/2015 3:08:07 PM | P | PASS |
|
|
permit finaled
|
BLD15-04096
| FIRE-Final Inspection | 11/30/2015 | 12/2/2015 | 12/2/2015 2:37:41 PM | A | FAIL |
|
|
Provide single action hardware on the rear exit door, remove the thumbturn dead bolt from the main exit door and provide sticker. Plans say "yes" for exit signage and that two exits are required. Provide exit signs as discussed or contact plan review for alternatives.
|
BLD13-03602
| FIRE-Final Inspection | 12/1/2015 | 12/2/2015 | 12/2/2015 10:09:33 AM | A | PASS |
|
|
Life safety passed. Provide correct single action hardware prior to a building inspection.
|
BLD15-04227
| FIRE-Final Inspection | 12/1/2015 | 12/2/2015 | 12/2/2015 8:38:27 AM | A | PASS |
|
|
Life safety passed
|
BLD15-03461
| FIRE-Final Inspection | 12/1/2015 | 12/2/2015 | 12/2/2015 7:22:44 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Todd Mathews Inspection cancelled from web by: Todd Mathews
|