Inspections for the day of: Wednesday, December 2, 2015.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00821 INSP-Sprinkler Rough-in/Hydro12/2/201512/2/201512/2/2015 3:28:06 PMPPART
Rough-in installation looks good except the new pendants that have been added in the soffit that was not shown on the plans need to meet NFPA 13-8.6.4.1.1.3. Plans/hydraulic calculations will need to be verified by plan review.
FIR15-00842 INSP-Final Inspection12/2/201512/2/201512/2/2015 3:08:07 PMPPASS
permit finaled
BLD15-04096 FIRE-Final Inspection11/30/201512/2/201512/2/2015 2:37:41 PMAFAIL
Provide single action hardware on the rear exit door, remove the thumbturn dead bolt from the main exit door and provide sticker. Plans say "yes" for exit signage and that two exits are required. Provide exit signs as discussed or contact plan review for alternatives.
BLD13-03602 FIRE-Final Inspection12/1/201512/2/201512/2/2015 10:09:33 AMAPASS
Life safety passed. Provide correct single action hardware prior to a building inspection.
BLD15-04227 FIRE-Final Inspection12/1/201512/2/201512/2/2015 8:38:27 AMAPASS
Life safety passed
BLD15-03461 FIRE-Final Inspection12/1/201512/2/201512/2/2015 7:22:44 AMACANC
Phone #: ###-#### >> Inspection requested via web by Todd Mathews Inspection cancelled from web by: Todd Mathews