Inspections for the day of: Monday, December 20, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01262 FIRE-Sprinkler Rough-in12/17/200412/20/200412/20/2004 12:00:00 AMAPASS
Sprinkler piping is ok to cover 12/20/2004 9:28:05 AM
BLD02-01499 FIRE-Final Inspection12/17/200412/20/200412/20/2004 12:00:00 AMAFAIL
Per fire dept review note #3 a fire hydrant is shown on sheet #1. That sheet is missing from the plans. Provide the missing sheet for hydrant verification. Provide waterflow verification per review note #4. Targee street must be open for fire dept access. See review note #5. Provide building address per review note #8. Provide ada approved door hardware on all doors per review note #10. Thumbturns are not allowed. Provide annual inspection for all fire extinguishers. See review note #9 12/20/2004 10:21:15 AM
FIR04-00552 INSP-Sprinkler Rough-in/Hydro12/20/200412/20/200412/20/2004 12:00:00 AMAPASS
Sprinkler piping in the entry and main corridor is ok to cover
BLD04-00815 FIRE-Final Inspection12/20/200412/20/200412/20/2004 12:00:00 AMPFAIL
Provide exit discharge lighting on the main exit and from classroom 5. Provide annual inspection for the fire extinguishers and provide approved door hardware for all doors in basement 12/20/2004 4:09:11 PM
FIR04-00368 INSP-Sprinkler Rough-in/Hydro12/20/200412/20/200412/20/2004 12:00:00 AMPPASS
Concealed pockets ok to cover 12/20/2004 2:08:06 PM
FIR04-00626 INSP-Sprinkler Rough-in/Hydro12/17/200412/20/200412/20/2004 12:00:00 AMPPART
Upright sprinkler head is overspaced under the east stairway. Provide the correct size of hanger rings on the trapeze and resubmit plans showing the steel pipe instead of the plastic and the branchline that was added 12/20/2004 12:04:59 PM
FIR04-00617 INSP-Alarm Testing12/17/200412/20/200412/20/2004 12:00:00 AMPFAIL
Ran out time to finish inspection. Phone lines tested ok. No other items tested. 12 volt side of the panel needs 12 amp hour battery. Did not test the 24 volt side. 24 volt side does not supervise both batteries per nfpa 72. 12/20/2004 4:08:18 PM