Inspections for the day of: Tuesday, December 20, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04101 Final12/19/200512/20/200512/20/2005 4:27:44 PMPPASS
jeremah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles signed occ card, ok to final
ELE05-04556 Rough-In Permanent Service12/20/200512/20/200512/20/2005 3:00:34 PMPFAIL
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called, left message, left corr notice,334.80 over 2 nm cables in draft stopped hole shall be derated, 312.5 conductors entering enclosures shall be protected from abrasion, 300.4(A) & (D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 725.55 cl 2 & 3 cable shall not be run with class 1 conductors, 110.14 splices shall be properly installed and used (crimper), BCC job id sticker shall be posted, address shall be posted, approved set of plans shall be on job
ELE05-04399 Rough-In Permanent Service12/20/200512/20/200512/20/2005 2:26:27 PMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr to restaple 1 box, ric ok p/s u/g n ok
ELE05-04102 Final12/19/200512/20/200512/20/2005 2:08:48 PMPPASS
jeremah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles signed occ card, left survey, 605.3 all wireways shall be provided and wiring contained within, 605.2(B) all other articles of nec shall apply, 110.12(A) unused openings shall be closed
ELE04-03764 ELE-Aging Inspection12/20/200512/20/200512/20/2005 9:53:38 AM DONE
see final
ELE04-03628 ELE-Aging Inspection12/20/200512/20/200512/20/2005 9:42:25 AM PASS
see final
ELE05-03331 Final12/20/200512/20/200512/20/2005 9:35:23 AMPCANC
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy done am
ELE05-03914 Final12/20/200512/20/200512/20/2005 9:33:30 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called contr, ok to final
ELE05-03331 Final12/19/200512/20/200512/20/2005 9:08:20 AMAPASS
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to final
ELE05-04492 Electrical Rough-In12/20/200512/20/200512/20/2005 8:08:15 AMAPASS
Scheduled by a contractor via Hello! on 12/20/2005 at 7:08:56 AM. Contact: ###-####. walls only ok to cover
ELE04-03628 Final12/20/200512/20/200512/20/2005 12:00:00 AMPPASS
ok to final
ELE04-03764 Final12/20/200512/20/200512/20/2005 12:00:00 AMPPASS
ok to final
ELE05-04467 Electrical Rough-In12/20/200512/20/200512/20/2005 12:00:00 AMPCANC
todd Note: ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cancelled to concrete