ELE06-03619
| Final | 12/20/2006 | 12/20/2006 | 12/20/2006 4:10:27 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day called, left corr notice, Told builder that there is not supposed to be an occupant prior to inspection. NEC 314.23 (A) boxes shall be securely mounted, 406.4(D) recpt faces shall be flush with or project from faceplates, 422.31(B) dishwasher shall have lock out provisions, 110.12(C) gfci in mbr shall not be damaged or deteriorated,BCC all work shall be done, disposal wired, a/c wired
|
ELE06-04657
| Temporary Service | 12/20/2006 | 12/20/2006 | 12/20/2006 4:04:16 PM | P | FAIL |
|
|
lynn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 314.23 boxes shall be securely mounted, BCC job address shall be posted, job id sticker shall be posted
|
ELE06-04635
| Electrical Rough-In | 12/19/2006 | 12/20/2006 | 12/20/2006 4:00:15 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/19/2006 at 1:00:15 PM. Contact: ###-####. called left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be stapled within 8" of box, 314.23 boxes shall be securely fastened, 110.12(C) casble shall not be damaged by tub, BCC all make-up shall be done
|
ELE06-03395
| Final | 12/20/2006 | 12/20/2006 | 12/20/2006 3:35:13 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 12/20/2006 at 7:03:40 AM. Contact: ###-####. gate 20 ok for final
|
ELE06-04641
| Electrical Rough-In | 12/20/2006 | 12/20/2006 | 12/20/2006 2:45:29 PM | P | PASS |
|
|
Please call Paul @###-#### before going to site so I can make sure access is available. thank you. Internet Inspection Request from: Paul Young ric ok
|
ELE06-04578
| Electrical Rough-In | 12/20/2006 | 12/20/2006 | 12/20/2006 2:11:20 PM | P | PASS |
|
|
Thank you; Phone #: ###-#### Internet Inspection Request from: steven sewell told contr to add recpt in 2' wall, ric ok
|
ELE06-04578
| Permanent Service | 12/20/2006 | 12/20/2006 | 12/20/2006 2:10:31 PM | P | PASS |
|
|
Thanks; Phone #: ###-#### Internet Inspection Request from: steven sewell told contr to add water pipe ground, guy kit, abrasion protection, p/s o/h rec ok
|
ELE06-03494
| Final | 12/19/2006 | 12/20/2006 | 12/20/2006 12:01:28 PM | A | NR |
|
|
Jason Note: call before; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett no furnture info yet, nec 605.7 multiwire ckts shall be disconnected simultaneously at panel
|
ELE06-04093
| Final | 12/19/2006 | 12/20/2006 | 12/20/2006 11:59:25 AM | A | FAIL |
|
|
John Note: call 30 min before insp; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett left corr notice, told elect, nec 605.7 multi-wire ckts shall be disconnected at panel simultaneously, 300.11(A) cables shall not be supported by grid, BCC no violations shall be retained
|
ELE06-03495
| Final | 12/19/2006 | 12/20/2006 | 12/20/2006 11:56:57 AM | A | PASS |
|
|
Jason Note: call before; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ok to final, no card
|
ELE06-04010
| Final | 12/19/2006 | 12/20/2006 | 12/20/2006 11:56:15 AM | A | PASS |
|
|
Jason Note: call before; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ok to final, signed occ card
|
ELE06-03693
| Final | 12/19/2006 | 12/20/2006 | 12/20/2006 10:34:23 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/19/2006 at 10:50:55 AM. Contact: ###-####. called left corr notice on panel, nec 110.26(A)(2) width of work space shall be 30" in front of panel
|
ELE06-03550
| Electrical Rough-In | 12/19/2006 | 12/20/2006 | 12/20/2006 12:00:00 AM | A | CANC |
|
|
Jason Note: call before; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett
|