Inspections for the day of: Wednesday, December 20, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00292 FIR-Aging Inspection12/20/200612/20/200612/26/2006 11:25:26 AM DONE
wip
FIR05-00695 INSP-Alarm Testing12/19/200612/20/200612/21/2006 8:56:23 AMAPART
Alarm tested satisfactory for the 6th floor guest rooms and common corridor areas. Sprinkler monitoring, elvator lobby, FJ remain to be tested on this floor. Also retested defficiencies on the 7th floor, the added SD in room 728 has not yet been programed, signage is to be provided at the visible "door chime" in the HC accessible room, noted voice evac in the guest rooms does not function on general alarm.
BLD06-03412 FIRE-Conference12/20/200612/20/200612/21/2006 8:47:31 AMPDONE
FIR06-00421 INSP-Final Inspection12/19/200612/20/200612/21/2006 8:46:43 AMPNR
Project is not completed for final inspection at this time.
FIR06-00653 INSP-Final Inspection12/19/200612/20/200612/20/2006 2:28:23 PMADEFR
No time to complete this inspection today, rescheduled per conversation with contractor.
BLD06-00384 FIRE-Final Inspection12/20/200612/20/200612/20/2006 2:26:07 PMPPASS
Fire life safety inspection passed.
FIR06-00270 INSP-Final Inspection12/19/200612/20/200612/20/2006 2:25:38 PMAPASS
Final fire alarm test is satisfactory, permit finaled.
BLD06-01354 FIRE-Final Inspection12/19/200612/20/200612/20/2006 11:29:14 AMADEFR
No time available to complete this inspection today, to be rescheduled per agreement with contractor.
BLD06-01625 FIRE-Conference12/19/200612/20/200612/20/2006 11:28:09 AMADONE
Confrence to discuss building addressing.
BLD06-00824 FIRE-Conference12/19/200612/20/200612/20/2006 11:13:22 AMADONE
On site discussion regarding fire code review note requirements for fire lane marking at the looped access road.
BLD06-02699 FIRE-Final Inspection12/19/200612/20/200612/20/2006 10:23:57 AMAFAIL
Duct detectors are not powered to enable testing or functionality.
FIR06-00671 INSP-Sprinkler Rough-in/Hydro12/19/200612/20/200612/20/2006 10:17:02 AMAPART
Overhead hydrostatic test passed. Noted two heads at the entryway high ceiling area which exceed max. allowable 130ft/2 for this system, the FDC ball drip will not function properly as installed, missing one flex coupling at the 21/2 feed to the lower office area where it passes through the floor, ssu's below the stairs at two locations are not installed, the remainder of system rough-in appears acceptable.