BLD06-02883
| FIRE-Final Inspection | 12/20/2006 | 12/20/2006 | 12/21/2006 8:21:57 AM | P | FAIL |
|
|
Need to final the fire alarm permit. No life safety inspection performed.
|
FIR06-00878
| INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/21/2006 8:20:57 AM | P | FAIL |
|
|
Need to provide an a/v in the breakroom, attach wire to structure and resubmit drawings showing wall changes and device relocations.
|
FIR05-00271
| INSP-Sprinkler Rough-in | 12/19/2006 | 12/20/2006 | 12/21/2006 7:44:08 AM | A | PART |
|
|
Sprinkler rough-in is mostly passed. Four overspaced heads were relocated while I performed the inspection. The first floor sprinkler piping can be covered except the garage as marked on the plans where the 1 1/2" main has actually be installed with with 2". Additional heads have been installed in closets that weren't shown in the first floor lobby. The second floor is ok to cover. The third floor can not be covered until a tenting inspection has been performed. Also on the third floor additional heads have been added in the bedrooms. One of these bedrooms is a remote area. Plans need to be resubmitted showing all of the addtional heads and piping reroutes. Also revised hydraulic calculations need to be resubmitted to verify the pipe size change on the first floor and the additional head that may need to be included in the remote area on the third floor.
|
BLD06-01696
| FIRE-Final Inspection | 12/20/2006 | 12/20/2006 | 12/20/2006 2:38:33 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00534
| INSP-Final Inspection | 12/20/2006 | 12/20/2006 | 12/20/2006 2:38:01 PM | P | PASS |
|
|
permit finaled
|
BLD06-02064
| FIRE-Final Inspection | 12/20/2006 | 12/20/2006 | 12/20/2006 12:58:27 PM | P | PASS |
|
|
Life safety finaled
|
FIR05-00714
| INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/20/2006 12:46:30 PM | P | PASS |
|
|
Permit finaled
|
FIR06-00548
| INSP-Sprinkler Rough-in/Hydro | 12/19/2006 | 12/20/2006 | 12/20/2006 10:41:28 AM | A | FAIL |
|
|
Overhead hydro test failed.
|
FIR06-00135
| INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/20/2006 10:28:35 AM | A | PASS |
|
|
Permit finaled
|
FIR05-00613
| INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/20/2006 10:28:18 AM | A | PASS |
|
|
Permit finaled
|
FIR06-00630
| INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/20/2006 10:27:27 AM | A | PASS |
|
|
permit finaled
|
FIR06-00491
| INSP-Alarm Testing | 12/19/2006 | 12/20/2006 | 12/20/2006 12:00:00 AM | P | DONE |
|
|
Jason Note: schedule for mid afternoon; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett
|