Inspections for the day of: Wednesday, December 20, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02883 FIRE-Final Inspection12/20/200612/20/200612/21/2006 8:21:57 AMPFAIL
Need to final the fire alarm permit. No life safety inspection performed.
FIR06-00878 INSP-Final Inspection12/19/200612/20/200612/21/2006 8:20:57 AMPFAIL
Need to provide an a/v in the breakroom, attach wire to structure and resubmit drawings showing wall changes and device relocations.
FIR05-00271 INSP-Sprinkler Rough-in12/19/200612/20/200612/21/2006 7:44:08 AMAPART
Sprinkler rough-in is mostly passed. Four overspaced heads were relocated while I performed the inspection. The first floor sprinkler piping can be covered except the garage as marked on the plans where the 1 1/2" main has actually be installed with with 2". Additional heads have been installed in closets that weren't shown in the first floor lobby. The second floor is ok to cover. The third floor can not be covered until a tenting inspection has been performed. Also on the third floor additional heads have been added in the bedrooms. One of these bedrooms is a remote area. Plans need to be resubmitted showing all of the addtional heads and piping reroutes. Also revised hydraulic calculations need to be resubmitted to verify the pipe size change on the first floor and the additional head that may need to be included in the remote area on the third floor.
BLD06-01696 FIRE-Final Inspection12/20/200612/20/200612/20/2006 2:38:33 PMPPASS
life safety finaled
FIR06-00534 INSP-Final Inspection12/20/200612/20/200612/20/2006 2:38:01 PMPPASS
permit finaled
BLD06-02064 FIRE-Final Inspection12/20/200612/20/200612/20/2006 12:58:27 PMPPASS
Life safety finaled
FIR05-00714 INSP-Final Inspection12/19/200612/20/200612/20/2006 12:46:30 PMPPASS
Permit finaled
FIR06-00548 INSP-Sprinkler Rough-in/Hydro12/19/200612/20/200612/20/2006 10:41:28 AMAFAIL
Overhead hydro test failed.
FIR06-00135 INSP-Final Inspection12/19/200612/20/200612/20/2006 10:28:35 AMAPASS
Permit finaled
FIR05-00613 INSP-Final Inspection12/19/200612/20/200612/20/2006 10:28:18 AMAPASS
Permit finaled
FIR06-00630 INSP-Final Inspection12/19/200612/20/200612/20/2006 10:27:27 AMAPASS
permit finaled
FIR06-00491 INSP-Alarm Testing12/19/200612/20/200612/20/2006 12:00:00 AMPDONE
Jason Note: schedule for mid afternoon; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett