BLD07-01877
| FIRE-Final Inspection | 12/19/2007 | 12/20/2007 | 12/21/2007 9:07:26 AM | P | FAIL |
|
|
Need to repair two exit lights, missing EM lighting at the south exit corridor, need project related fire alarm permit finaled, jobsite is not in condition at this time for final life safety approval.
|
FIR07-00950
| INSP-Final Inspection | 12/19/2007 | 12/20/2007 | 12/21/2007 9:04:53 AM | P | FAIL |
|
|
Pull stations at two locations are above max. height limit, notification device testing passed.
|
FIR06-00838
| INSP-Final Inspection | 12/20/2007 | 12/20/2007 | 12/20/2007 2:34:10 PM | P | PASS |
|
|
All corrections made per forest notes.KR
|
BLD07-02968
| FIRE-Final Inspection | 12/18/2007 | 12/20/2007 | 12/20/2007 1:02:51 PM | P | PASS |
|
|
Fire life safety is satisfactory.
|
FIR07-01015
| INSP-Final Inspection | 12/19/2007 | 12/20/2007 | 12/20/2007 1:01:58 PM | P | PASS |
|
|
Fire alarm interconnection passed testing, noted an updated building map will be required at the FACP-to be provided and verified as discussed, permit finaled.
|
FIR06-00838
| INSP-Final Inspection | 12/19/2007 | 12/20/2007 | 12/20/2007 11:59:00 AM | A | FAIL |
|
|
Heads at three locations are blocked by ceiling mounted obstructions and do not meet criteria per 8.10.6.1.2 NFPA 13 2002. UG supply flush completed okay.
|