Inspections for the day of: Tuesday, December 20, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00627 INSP-Final Inspection12/19/201112/20/201112/22/2011 11:16:39 AMAPASS
permit finaled
BLD11-02386 FIRE-Final Inspection12/19/201112/20/201112/20/2011 3:53:08 PMPFAIL
Will be able to final life safety when the project related fire alarm permit is finaled.
FIR11-00670 INSP-Final Inspection12/20/201112/20/201112/20/2011 3:51:04 PMPCANC
canceled due to time constraints.
BLD11-02962 FIRE-Final Inspection12/20/201112/20/201112/20/2011 3:48:35 PMPCANC
canceled due to time constraints.
FIR11-00661 INSP-Final Inspection12/20/201112/20/201112/20/2011 3:42:52 PMPFAIL
The new horn/strobes that have been installed are not the devices that have been submitted. Also as-built plans were not provided as required due to the NAC errors. Provide a data sheet for the new devices to plan review and as-builts.
FIR11-00605 INSP-Final Inspection12/20/201112/20/201112/20/2011 3:32:22 PMPPASS
Permit finaled
FIR11-00643 INSP-Final Inspection12/19/201112/20/201112/20/2011 3:32:00 PMPPASS
Permit finaled. The hood suppression system functioned correctly.
FIR11-00579 INSP-Sprinkler Rough-in/Hydro12/19/201112/20/201112/20/2011 2:02:58 PMPPASS
24 hour air test and forward flush passed. First floor office area piping can be covered.
BLD11-02914 FIRE-Final Inspection12/20/201112/20/201112/20/2011 12:16:36 PMPFAIL
Not ready for inspection
BLD11-02695 FIRE-Final Inspection12/19/201112/20/201112/20/2011 11:15:39 AMPPASS
life safety passed. One additional smoke alarm needs to be installed outside of the sleeping room. Battery powered is ok. Building inspector please verify.
BLD11-02363 FIRE-Final Inspection12/19/201112/20/201112/20/2011 10:46:48 AMPPASS
life safety passed
FIR11-00663 INSP-Final Inspection12/20/201112/20/201112/20/2011 10:21:42 AMPPASS
permit finaled
FIR11-00607 INSP-Sprinkler Rough-in12/20/201112/20/201112/20/2011 10:17:22 AMPPASS
24 hr pressure test started 10:00 with 42 1/2 psi
FIR11-00621 INSP-Sprinkler Rough-in/Hydro12/19/201112/20/201112/19/2011 2:44:31 PMAPASS
UG supply line hydro test passed