Inspections for the day of: Tuesday, December 20, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02945 Final12/19/201612/20/201612/20/2016 1:54:10 PMPFAIL
Matt Phone #: ###-####-please call with a meet time
Homeowner covered with drywall prior to approval. Only items unable to confirm completed are NM abrasion protection and securing near boxes. After asking owner questions of how he completed corrections I believe them to be completed.
110.3- Fittings for EMT installed on water heater shall be listed for EMT.
422.30- A disconnecting means shall be installed on water heater circuit. 110.25 lockout acceptable.
Complete and call for final
ELE16-00489 Final12/19/201612/20/201612/20/2016 10:31:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat
Final ok
ELE16-04070 Rough-In Permanent Service12/20/201612/20/201612/20/2016 9:26:44 AMAFAIL
ROUGH IN HOUSE AND GARAGE. PERMANENT SERVICE Phone #: ###-#### Inspection requested via web by mike brown
* No access to loft above garage.
300.15- All outdoor receptacle outlets shall have boxes. Light under stair wire not in box.
300.4- SER above panel needs nail plates.
230.79- 50 amp installed and labelled for garage, shall be 60 amp minimum
ELE16-04043 Rough-In Permanent Service12/16/201612/20/201612/20/2016 8:51:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson
Receptacle needed master bed behind door, pocket door will create 5' wall space. Will check on final.
Rough in ok cover p/s u/g n ok