Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00611 INSP-Final Inspection12/19/201612/20/201612/20/2016 2:41:10 PMPPASS
Final inspection for CO2 system interface with premise fire panel passed/complete.
FIR16-00521 INSP-Final Inspection12/19/201612/20/201612/20/2016 2:40:29 PMPPASS
Final inspection for CO2 fire suppression system passed/complete.
FIR16-00510 INSP-Sprinkler Rough-in/Hydro12/20/201612/20/201612/20/2016 1:19:24 PMPPART
Rough to cover inspection for overhead fire sprinkler piping complete for levels 3 and 4, all overhead fire sprinkler piping on level 4 approved for cover, will need to verify heat for breezeway crossings at a later date, overhead fire sprinkler piping located between floor levels on level 3 approved for cover, tenting was not installed over piping in attic space on level 3 so piping located in attic space on level 3 cannot be covered until tenting is installed and inspected. Hydrostatic test for overhead fire sprinkler piping on levels 3 and 4 passed/complete.
FIR16-00801 INSP-Final Inspection12/20/201612/20/201612/20/2016 11:22:15 AMPPASS
Final inspection for fire sprinklers in area of work complete, noted at time of inspection inside temperature of building was 40 degree's at thermostat, instructed property representative that the temperature needs to maintained at 40 degree's or above for system protection.
BLD16-00147 FIRE-Final Inspection12/20/201612/20/201612/20/2016 11:19:26 AMPPART
Partial final life fire safety inspection for TCO complete for levels 1 and 2, fire sprinkler inspection complete (fire sprinklers are active) for fire pump room as well as levels 1, 2 and 3 fire sprinklers including wet standpipes for both east and west stairwells, fire alarm inspection complete for levels 1, 2 and 3 (was instructed at time of alarm inspection that fire panel will be monitored for the requested occupied area's) including automatic function for stairwell pressurization. Temporary fire extinguishers are in place for levels 1, 2 and 3, permanent extinguishers will be put in place at a later date, knox box is in place, final inspection for commercial hood fire suppression system complete. Partial final inspection for TCO inspection complete.
BLD16-00147 FIRE-Supply Line Cover12/20/201612/20/201612/20/2016 10:38:35 AMPCANC
Inspection request is for TCO inspection for levels 1,2 and 3, this inspection request is cancelled and the correct inspection request will be generated.
FIR16-00600 INSP-Final Inspection12/19/201612/20/201612/20/2016 10:33:05 AMAPASS
Final commercial hood fire suppression system inspection passed/complete.