Inspections for the day of: Wednesday, December 20, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03883 Final12/19/201712/20/201712/20/2017 3:41:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Aaron Decker...ok to final
ELE17-02649 Electrical Rough-In12/18/201712/20/201712/20/2017 3:35:05 PMPPASS
contact Andy CHambers Phone #: ###-#### Inspection requested via web by Scott Campbell..
patient room walls as marked on plans
ELE17-04201 Final12/20/201712/20/201712/20/2017 2:33:38 PMPPASS
Inspection requested via web by Christian Kilpatrick...Labelling and OCPD ok...ok to final
ELE17-04276 Final12/20/201712/20/201712/20/2017 1:14:42 PMPNR
Pole is set in NE corner of lot next to monument sign. Phone #: ###-#### Inspection requested via web by Clint Tate...grounding not done
ELE17-04036 Final12/20/201712/20/201712/20/2017 1:01:43 PMPPASS
Michelle Phone #: ###-####...ok to final
ELE17-03465 Permanent Service12/20/201712/20/201712/20/2017 12:43:07 PMPPASS
New service tap from existing IP CT can. Ready for inspection.
Phone #: ###-#### Inspection requested via web by Sean Patton...p/s rec ok
ELE17-04228 Final12/19/201712/20/201712/20/2017 10:56:21 AMAPASS
Contact Seth VanWassenhove. Phone #: ###-#### Inspection requested via web by Cathy Duchek....inspection was for new underground to meter...meter and panel stayed original...contractor did upgrade grounding to code...ok to final
ELE17-04201 Electrical Rough-In12/19/201712/20/201712/20/2017 10:11:35 AMAPASS
Pls contact Spencer (Foreman) @ ###-#### or Barry (Electrician) @ ###-#### one hr prior or if you have questions. Thank you. Inspection requested via web by Christian Kilpatrick....
UL listed equipment verified
ELE17-03501 Final12/19/201712/20/201712/20/2017 9:29:30 AMAFAIL
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg...
1) oulets in master bedroom have open ground
2) plates missing thru out house
3) outlets in utillity room need GFI protection
4) master bedroom shall be ARC fault protected
outlets, lighting, and smoke detectors
5) new circuits to panel need labelled in panel
ELE17-02755 Final12/20/201712/20/201712/20/2017 8:50:38 AMAFAIL
Key Code - 7600 Phone #: ###-#### Inspection requested via web by Jerry Moore...
1) GFI will not set in exam room...110.7
2) outlets with no power in exam rm...110.7
3) open junction box...110.7, 314.28(C)
4) baried junction box behind cabinet...junction boxes shall be accessible...314.29
ELE17-04228 Electrical Rough-In12/19/201712/20/201712/19/2017 4:04:34 PMACANC
Contact Seth VanWassenhove Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek