ELE17-03883
| Final | 12/19/2017 | 12/20/2017 | 12/20/2017 3:41:31 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Aaron Decker...ok to final
|
ELE17-02649
| Electrical Rough-In | 12/18/2017 | 12/20/2017 | 12/20/2017 3:35:05 PM | P | PASS |
|
|
contact Andy CHambers Phone #: ###-#### Inspection requested via web by Scott Campbell.. patient room walls as marked on plans
|
ELE17-04201
| Final | 12/20/2017 | 12/20/2017 | 12/20/2017 2:33:38 PM | P | PASS |
|
|
Inspection requested via web by Christian Kilpatrick...Labelling and OCPD ok...ok to final
|
ELE17-04276
| Final | 12/20/2017 | 12/20/2017 | 12/20/2017 1:14:42 PM | P | NR |
|
|
Pole is set in NE corner of lot next to monument sign. Phone #: ###-#### Inspection requested via web by Clint Tate...grounding not done
|
ELE17-04036
| Final | 12/20/2017 | 12/20/2017 | 12/20/2017 1:01:43 PM | P | PASS |
|
|
Michelle Phone #: ###-####...ok to final
|
ELE17-03465
| Permanent Service | 12/20/2017 | 12/20/2017 | 12/20/2017 12:43:07 PM | P | PASS |
|
|
New service tap from existing IP CT can. Ready for inspection. Phone #: ###-#### Inspection requested via web by Sean Patton...p/s rec ok
|
ELE17-04228
| Final | 12/19/2017 | 12/20/2017 | 12/20/2017 10:56:21 AM | A | PASS |
|
|
Contact Seth VanWassenhove. Phone #: ###-#### Inspection requested via web by Cathy Duchek....inspection was for new underground to meter...meter and panel stayed original...contractor did upgrade grounding to code...ok to final
|
ELE17-04201
| Electrical Rough-In | 12/19/2017 | 12/20/2017 | 12/20/2017 10:11:35 AM | A | PASS |
|
|
Pls contact Spencer (Foreman) @ ###-#### or Barry (Electrician) @ ###-#### one hr prior or if you have questions. Thank you. Inspection requested via web by Christian Kilpatrick.... UL listed equipment verified
|
ELE17-03501
| Final | 12/19/2017 | 12/20/2017 | 12/20/2017 9:29:30 AM | A | FAIL |
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg... 1) oulets in master bedroom have open ground 2) plates missing thru out house 3) outlets in utillity room need GFI protection 4) master bedroom shall be ARC fault protected outlets, lighting, and smoke detectors 5) new circuits to panel need labelled in panel
|
ELE17-02755
| Final | 12/20/2017 | 12/20/2017 | 12/20/2017 8:50:38 AM | A | FAIL |
|
|
Key Code - 7600 Phone #: ###-#### Inspection requested via web by Jerry Moore... 1) GFI will not set in exam room...110.7 2) outlets with no power in exam rm...110.7 3) open junction box...110.7, 314.28(C) 4) baried junction box behind cabinet...junction boxes shall be accessible...314.29
|
ELE17-04228
| Electrical Rough-In | 12/19/2017 | 12/20/2017 | 12/19/2017 4:04:34 PM | A | CANC |
|
|
Contact Seth VanWassenhove Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
|